Human response to five designs of personalized ventilation

被引:75
作者
Kaczmarczyk, J [1 ]
Melikov, A
Bolashikov, Z
Nikolaev, L
Fanger, PO
机构
[1] Tech Univ Denmark, Dept Mech, Int Ctr Indoor Environm & Energy, DK-2800 Lyngby, Denmark
[2] Silesian Tech Univ, Dept Heating Ventilat & Dust Removal Technol, Gliwice, Poland
来源
HVAC&R RESEARCH | 2006年 / 12卷 / 02期
关键词
D O I
10.1080/10789669.2006.10391184
中图分类号
O414.1 [热力学];
学科分类号
摘要
Human response to five different air terminal devices (ATDs) for a personalized ventilation system (PVS) was studied in an experimental office under well-defined conditions. A group of 30 human subjects assessed air quality and rated their thermal comfort and perception of draft. Two temperature levels, 23 degrees C and 26 degrees C, and two background levels of air quality in the office, high and low, were studied during the experiments. Under all conditions the personalized ventilation system provided outdoor air at a temperature of 20 degrees C. All PVSs allowed for individual control of the airflow rate as well as for adjustments of the supply air direction. Results showed that all ATDs studied significantly improved perceived air quality at the workstation. The greatest improvement was obtained when the pollution level and the temperature in the office were high. The thermal environment created with all systems was assessed as acceptable. Subjects were able to improve thermal comfort with all ATDs studied. The subjects identified which of the tested ATDs they preferred.
引用
收藏
页码:367 / 384
页数:18
相关论文
共 31 条
  • [1] AKIMOTO T, 2004, P ROOMV 2004 COIMBR
  • [2] [Anonymous], ASHVE T
  • [3] [Anonymous], 2004, 55 ASHRAE
  • [4] [Anonymous], ASHVE T
  • [5] [Anonymous], 1752 CEN CR EUR COMM
  • [6] [Anonymous], 1993, 7730 ISO
  • [7] ASHRAE, 2005, ASHRAE HDB FUND
  • [8] Bolashikov Z, 2003, P HLTH BUILD 2003, V2, P850
  • [9] Impact of temperature and humidity on perception of indoor air quality during immediate and longer whole-body exposures
    Fang, L
    Clausen, G
    Fanger, PO
    [J]. INDOOR AIR-INTERNATIONAL JOURNAL OF INDOOR AIR QUALITY AND CLIMATE, 1998, 8 (04): : 276 - 284
  • [10] Impact of temperature and humidity on the perception of indoor air quality
    Fang, L
    Clausen, G
    Fanger, PO
    [J]. INDOOR AIR-INTERNATIONAL JOURNAL OF INDOOR AIR QUALITY AND CLIMATE, 1998, 8 (02): : 80 - 90