Energy variance criterion and threshold tuning scheme for high impedance fault detection

被引:53
作者
Lien, KY [1 ]
Chen, SL
Guo, CJLTY
Shen, TMLJS
机构
[1] Natl Tsing Hua Univ, Dept Elect Engn, Hsinchu, Taiwan
[2] Taiwan Power Co, Power Res Inst, Taipei, Taiwan
[3] Taiwan Power Co, Yunlin Adm Div, Taipei, Taiwan
关键词
distribution feeder; high impedance fault; digital relaying; arcing fault; staged fault test dependability test; three-phase unbalanced current;
D O I
10.1109/61.772319
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents a new approach to the detection of high impedance fault (HIF). The proposed approach (or detector which implements this approach) has four distinct features. First, the detector input signal is the three-phase unbalanced current (or feeder 3I(0)), rather than the conventional three individual phase-currents. Secondly, the detector is designed by monitoring the energy variance for the second, fourth and sixth harmonics of 3I(0) individually, and by requiring the increment of randomness of all these harmonics to indicate an HIF. Thirdly, a self-tuning scheme based on the statistical confidence is applied to the automatic setting of threshold level for the energy variances monitored. Fourthly, effective counters are designed to detect both persistent and intermittent arcings. The detector has been tested on 51 staged faults and 8 unfaulted feeders. The test results show that the detector can have 100% fault detection rate so long as the arcing current at fault location is not less than 5A. As to the dependability tests, no false alarm (or tripping) has happened for all of the unfaulted feeders under test. These feeders either supply special (including are furnace) load, or have leakage current (referring to the intermittent zero-sequence load due to the feeder location along coast), or are under the normal capacitor or load switchings. The test results and the investigation for the high sensitivity and dependability and for the limitation of proposed fault detection method are presented.
引用
收藏
页码:810 / 817
页数:8
相关论文
共 14 条
[1]   DETECTION OF DISTRIBUTION HIGH IMPEDANCE FAULTS USING BURST NOISE SIGNALS NEAR 60 HZ [J].
AUCOIN, M ;
RUSSELL, BD .
IEEE TRANSACTIONS ON POWER DELIVERY, 1987, 2 (02) :342-348
[2]   IMPROVED ALGORITHM FOR DETECTING ARCING FAULTS USING RANDOM FAULT BEHAVIOR [J].
BENNER, C ;
CARSWELL, P ;
RUSSELL, BD .
ELECTRIC POWER SYSTEMS RESEARCH, 1989, 17 (01) :49-56
[3]   HIGH IMPEDANCE FAULT-TESTS ON THE TAIPOWER PRIMARY DISTRIBUTION-SYSTEM [J].
CHU, HY ;
CHEN, MT ;
HUANG, CL ;
CHEN, SL ;
YEN, SS .
ELECTRIC POWER SYSTEMS RESEARCH, 1990, 19 (02) :105-114
[4]   ALGORITHM COMPARISON FOR HIGH IMPEDANCE FAULT-DETECTION BASED ON STAGED FAULT TEST [J].
HUANG, CL ;
CHU, HY ;
CHEN, MT .
IEEE TRANSACTIONS ON POWER DELIVERY, 1988, 3 (04) :1427-1435
[5]  
*IEEE, 1990, IEEE PUBL
[6]   HARMONIC BEHAVIOR DURING ARCING FAULTS ON POWER DISTRIBUTION FEEDERS [J].
KIM, CJ ;
RUSSELL, BD .
ELECTRIC POWER SYSTEMS RESEARCH, 1988, 14 (03) :219-225
[7]  
LIEN KY, 1994, METHOD DESIGN IMPLEM
[8]  
LIEN KY, 1993, P 3 INT S EL EN MAN, P386
[9]  
LIEN KY, 1997, PERFORMANCE TESTING
[10]   SIGNATURES AND SOFTWARE FIND HIGH IMPEDANCE FAULTS [J].
PATTERSON, R .
IEEE COMPUTER APPLICATIONS IN POWER, 1995, 8 (03) :12-15