Evaluation of Transformer Insulation by Frequency Domain Technique

被引:6
|
作者
Poovamma, P. K. [1 ]
Sudhindra, A. [1 ]
Mallikarjunappa, K. [1 ]
Ahamad, T. R. Afzal [1 ]
机构
[1] Cent Power Res Inst, Bangalore, Karnataka, India
来源
2007 IEEE INTERNATIONAL CONFERENCE ON SOLID DIELECTRICS, VOLS 1 AND 2 | 2007年
关键词
D O I
10.1109/ICSD.2007.4290905
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Measurements of Dielectric Response in Frequency domain is being employed for assessing the condition of the paper-oil insulation system in Transformers. The laboratory measurements were carried out on Models based on simple Transformer insulation system. The dependence of frequency, temperature, voltage and ageing of the insulation system on the spectral behaviour of dielectric responses are discussed. The paper also present: correlation and comparison of the laboratory results, to the measurements performed on in-service Power Transformers. The healthiness of the insulation system of the in-service Transformers were evaluated arc recommendations were made to improve the condition of the insulation system to extend the service life of the Transformers.
引用
收藏
页码:681 / 684
页数:4
相关论文
共 50 条
  • [31] Effect of measurement temperature on power transformer insulation diagnosis using frequency-domain spectroscopy
    Dutta, Saurabh
    Baral, Arijit
    Pradhan, Arpan Kumar
    Chakravorti, Sivaji
    IET SCIENCE MEASUREMENT & TECHNOLOGY, 2017, 11 (06) : 773 - 779
  • [32] Research on Nonlinear Characteristics for Frequency Domain Dielectric Response of Transformer Oil-paper Insulation
    Zhang M.
    Meng F.
    Liu J.
    Liu H.
    Jia H.
    Li L.
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2023, 43 (02): : 831 - 842
  • [33] Research on nonlinear characteristics for frequency domain dielectric response of transformer oil-paper insulation
    Zhang, Mingze
    Lei, Shengjie
    Liu, Heqian
    Shen, Yubo
    Liu, Ji
    Shi, Yunbo
    Jia, Haifeng
    Li, Lu
    MEASUREMENT, 2022, 204
  • [34] Application of frequency domain spectroscopy to the insulation diagnosis of oil-immersed power transformer on site
    Zhang, Zhi
    Dong, Ming
    Yang, Shuang-Suo
    Jiang, Wei
    Zhang, Guan-Jun
    Yan, Zhang
    Gaodianya Jishu/High Voltage Engineering, 2009, 35 (07): : 1648 - 1653
  • [35] Analysis of Distribution Transformer Insulation Using Domain Method
    Janura, Richard
    Jurcik, Jozef
    Gutten, Miroslav
    Korenciak, Daniel
    2014 ELEKTRO, 2014, : 294 - 297
  • [36] Research on Time Saving and Accurate Testing Techniques for Frequency Domain Spectroscopy of Transformer Oil Paper Insulation
    Zhang, Yiyi
    Mao, Xinyang
    Zhang, Xingtuo
    Xu, Chuqi
    Wang, Gang
    Li, Sheng
    IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, 2022, 71
  • [37] Investigation on frequency domain dielectric characteristics parameters for condition assessment of transformer oil-paper insulation
    Liao, Ruijin
    Liu, Jiefeng
    Yang, Lijun
    Ma, Zhiqin
    Gao, Fei
    Zhang, Yiyi
    Diangong Jishu Xuebao/Transactions of China Electrotechnical Society, 2015, 30 (06): : 247 - 254
  • [38] Equivalent Circuit Modelling of Transformer Oil-Paper Insulation from Frequency Domain Spectroscopy Measurements
    Chowdhury, S.
    Haque, N.
    Chatterjee, S.
    2020 3RD INTERNATIONAL CONFERENCE ON ENERGY, POWER AND ENVIRONMENT: TOWARDS CLEAN ENERGY TECHNOLOGIES (ICEPE 2020), 2021,
  • [39] Estimation of Activation Energy of Transformer Insulation from Frequency Domain Spectroscopy Measurement Performed at a Particular Temperature
    Chowdhury, Soumyadeep
    Haque, Nasirul
    Chatterjee, Soumya
    Pradhan, Arpan K.
    Chakravorti, Sivaji
    2021 IEEE ELECTRICAL INSULATION CONFERENCE (EIC), 2021, : 132 - 136
  • [40] Extraction of Frequency Domain Dielectric Characteristic Parameter of Oil-paper Insulation for Transformer Condition Assessment
    Liao, Ruijin
    Liu, Jiefeng
    Yang, Lijun
    Zhang, Yiyi
    Gao, Jun
    Ma, Zhiqing
    Hao, Jian