PMU-Based Fault Location Using Voltage Measurements in Large Transmission Networks

被引:109
|
作者
Jiang, Quanyuan [1 ]
Li, Xingpeng [1 ]
Wang, Bo [2 ]
Wang, Haijiao [1 ]
机构
[1] Zhejiang Univ, Coll Elect Engn, Hangzhou 310027, Zhejiang, Peoples R China
[2] Ningbo Elect Co State Grid, Ningbo 315000, Zhejiang, Peoples R China
关键词
Bus-impedance matrix; fault location; matching degree index; optimal phasor measurement unit (PMU) placement; voltage measurements; LINES;
D O I
10.1109/TPWRD.2012.2199525
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents a general fault-location method for large transmission networks which uses phasor measurement unit (PMU) voltage measurements where the injected current at a fault point can be calculated by using the voltage change and its relevant transfer impedance on any bus. A two-stage fault-location optimization model is proposed, along with defining a matching degree index. The first stage is the fault region identification stage, which uses the matching degree index to determine the suspicious fault region in order to reduce the search area. The second stage is used to identify the exact fault line and fault distance. A method to determine optimal PMU placement is also proposed in this paper. Case studies verify that the proposed fault-location algorithm and optimal PMU placement scheme can locate faults in large transmission networks quickly and accurately without requiring fault-type classification or fault phase selection.
引用
收藏
页码:1644 / 1652
页数:9
相关论文
共 50 条
  • [41] Iterative Fault Location Scheme for a Transmission Line Using Synchronized Phasor Measurements
    Brahma, Sukumar M.
    INTERNATIONAL JOURNAL OF EMERGING ELECTRIC POWER SYSTEMS, 2007, 8 (06):
  • [42] A closed-form solution for transmission line fault location using local measurements at a remote substation
    Dobakhshari, A. Salehi
    Ranjbar, A. M.
    ELECTRIC POWER SYSTEMS RESEARCH, 2014, 111 : 115 - 122
  • [43] A new algorithm for fault location on transmission lines by optimal PMU placement
    Jegarluei, Mohammad Rezaei
    Dobakhshari, Ahmad Salehi
    Ranjbar, Ali Mohammad
    Tayebi, Ali
    INTERNATIONAL TRANSACTIONS ON ELECTRICAL ENERGY SYSTEMS, 2015, 25 (10): : 2071 - 2086
  • [44] A Sparse-Data-Driven Approach for Fault Location in Transmission Networks
    Majidi, Mehrdad
    Etezadi-Amoli, Mehdi
    Fadali, Mohammed Sami
    IEEE TRANSACTIONS ON SMART GRID, 2017, 8 (02) : 548 - 556
  • [45] Improving the Fault Location for Transmission Grids using the Existing Measurements
    Dragomir, Marian
    Filip, Bogdan
    Dragomir, Alin
    2018 INTERNATIONAL CONFERENCE AND EXPOSITION ON ELECTRICAL AND POWER ENGINEERING (EPE), 2018, : 321 - 324
  • [46] Optimal Fault Location Algorithm for Series-Compensated Transmission Lines Based on PMU Data
    Mousavi-Seyedi, Seyed Sina
    Aminifar, Farrokh
    Rezaei, Mohammad Reza
    Hasani, Rahman
    2015 SMART GRID CONFERENCE (SGC 2015), 2015, : 105 - 109
  • [47] Distribution Network Fault Location Based on μPMU Information
    Wang X.
    Ren X.
    He J.
    Wang Z.
    Zhang Y.
    Shi Z.
    Chen D.
    Dianwang Jishu/Power System Technology, 2019, 43 (03): : 810 - 817
  • [48] Fault location in meshed power networks by using hybrid sparse current and voltage measurements along with RSFCL
    Shoaib, Muhammad Asim
    Khan, Abdul Qayyum
    Gul, Sufi Tabassum
    Mustafa, Ghulam
    Abid, Muhammad
    Abubakar, Muhammad
    Khan, Adil
    ELECTRIC POWER SYSTEMS RESEARCH, 2023, 225
  • [49] A Novel Method for Fault Location of Transmission Lines by Wide-Area Voltage Measurements Considering Measurement Errors
    Dobakhshari, A. Salehi
    Ranjbar, A. M.
    IEEE TRANSACTIONS ON SMART GRID, 2015, 6 (02) : 874 - 884
  • [50] Novel Fault Location Algorithm for Transmission Line using Synchronized Measurements
    Hinge, Trupti P.
    Dambhare, Sanjay S.
    2016 IEEE/PES TRANSMISSION AND DISTRIBUTION CONFERENCE AND EXPOSITION (T&D), 2016,