PMU-Based Fault Location Using Voltage Measurements in Large Transmission Networks

被引:109
|
作者
Jiang, Quanyuan [1 ]
Li, Xingpeng [1 ]
Wang, Bo [2 ]
Wang, Haijiao [1 ]
机构
[1] Zhejiang Univ, Coll Elect Engn, Hangzhou 310027, Zhejiang, Peoples R China
[2] Ningbo Elect Co State Grid, Ningbo 315000, Zhejiang, Peoples R China
关键词
Bus-impedance matrix; fault location; matching degree index; optimal phasor measurement unit (PMU) placement; voltage measurements; LINES;
D O I
10.1109/TPWRD.2012.2199525
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents a general fault-location method for large transmission networks which uses phasor measurement unit (PMU) voltage measurements where the injected current at a fault point can be calculated by using the voltage change and its relevant transfer impedance on any bus. A two-stage fault-location optimization model is proposed, along with defining a matching degree index. The first stage is the fault region identification stage, which uses the matching degree index to determine the suspicious fault region in order to reduce the search area. The second stage is used to identify the exact fault line and fault distance. A method to determine optimal PMU placement is also proposed in this paper. Case studies verify that the proposed fault-location algorithm and optimal PMU placement scheme can locate faults in large transmission networks quickly and accurately without requiring fault-type classification or fault phase selection.