PMU-Based Fault Location Using Voltage Measurements in Large Transmission Networks

被引:109
|
作者
Jiang, Quanyuan [1 ]
Li, Xingpeng [1 ]
Wang, Bo [2 ]
Wang, Haijiao [1 ]
机构
[1] Zhejiang Univ, Coll Elect Engn, Hangzhou 310027, Zhejiang, Peoples R China
[2] Ningbo Elect Co State Grid, Ningbo 315000, Zhejiang, Peoples R China
关键词
Bus-impedance matrix; fault location; matching degree index; optimal phasor measurement unit (PMU) placement; voltage measurements; LINES;
D O I
10.1109/TPWRD.2012.2199525
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents a general fault-location method for large transmission networks which uses phasor measurement unit (PMU) voltage measurements where the injected current at a fault point can be calculated by using the voltage change and its relevant transfer impedance on any bus. A two-stage fault-location optimization model is proposed, along with defining a matching degree index. The first stage is the fault region identification stage, which uses the matching degree index to determine the suspicious fault region in order to reduce the search area. The second stage is used to identify the exact fault line and fault distance. A method to determine optimal PMU placement is also proposed in this paper. Case studies verify that the proposed fault-location algorithm and optimal PMU placement scheme can locate faults in large transmission networks quickly and accurately without requiring fault-type classification or fault phase selection.
引用
收藏
页码:1644 / 1652
页数:9
相关论文
共 50 条
  • [21] Fault Location Estimation For Transmission Lines Using Voltage Sag Data
    Kang, Ning
    Liao, Yuan
    IEEE POWER AND ENERGY SOCIETY GENERAL MEETING 2010, 2010,
  • [22] Improvement of Fault Location Method Based on Sparse PMU Measurements
    Mouco, Arthur
    Abur, A.
    2017 NORTH AMERICAN POWER SYMPOSIUM (NAPS), 2017,
  • [23] Wide area fault location on transmission systems using synchronized/ unsynchronized voltage/current measurements
    Chafi, Zahra Shafiei
    Afrakhte, Hossein
    ELECTRIC POWER SYSTEMS RESEARCH, 2021, 197
  • [24] Fault Location for Transmission Lines with Voltage and Current Measurements at One Bus
    Xiu, Wanjing
    Liao, Yuan
    INTERNATIONAL JOURNAL OF EMERGING ELECTRIC POWER SYSTEMS, 2014, 15 (05) : 449 - 456
  • [25] Fault location scheme for a multi-terminal transmission line using synchronized voltage measurements
    Brahma, SM
    IEEE TRANSACTIONS ON POWER DELIVERY, 2005, 20 (02) : 1325 - 1331
  • [26] Fault localisation and diagnosis in transmission networks based on robust deep Gabor convolutional neural network and PMU measurements
    Afrasiabi, Shahabodin
    Afrasiabi, Mousa
    Mohammadi, Mohammad
    Parang, Benyamin
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2020, 14 (26) : 6484 - 6492
  • [27] Fault Location using PMU Measurements and Wide-area Infrastructure
    Picard, Stephan D.
    Adamiak, Mark G.
    Madani, Vahid
    2015 68TH ANNUAL CONFERENCE FOR PROTECTIVE RELAY ENGINEERS, 2015, : 272 - 277
  • [28] Fault Location in Distribution Networks Using PMU Data and Interval Algorithm
    Fang, Chen
    Shi, Zhixiong
    Peng, Yang
    Wu, Zhi
    Gu, Wei
    Nie, Pengchen
    2019 9TH INTERNATIONAL CONFERENCE ON POWER AND ENERGY SYSTEMS (ICPES), 2019,
  • [29] Fault Location for Distribution Networks Based on Node Voltage Equation
    Tan Dan
    Yang Honggeng
    2012 ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), 2012,
  • [30] Compensation of Systematic Errors for Improved PMU-Based Fault Detection and Location in Three-Phase Distribution Grids
    Pegoraro P.A.
    Sitzia C.
    Solinas A.V.
    Sulis S.
    Carta D.
    Benigni A.
    IEEE Transactions on Instrumentation and Measurement, 2024, 73