PMU-Based Fault Location Using Voltage Measurements in Large Transmission Networks

被引:109
|
作者
Jiang, Quanyuan [1 ]
Li, Xingpeng [1 ]
Wang, Bo [2 ]
Wang, Haijiao [1 ]
机构
[1] Zhejiang Univ, Coll Elect Engn, Hangzhou 310027, Zhejiang, Peoples R China
[2] Ningbo Elect Co State Grid, Ningbo 315000, Zhejiang, Peoples R China
关键词
Bus-impedance matrix; fault location; matching degree index; optimal phasor measurement unit (PMU) placement; voltage measurements; LINES;
D O I
10.1109/TPWRD.2012.2199525
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents a general fault-location method for large transmission networks which uses phasor measurement unit (PMU) voltage measurements where the injected current at a fault point can be calculated by using the voltage change and its relevant transfer impedance on any bus. A two-stage fault-location optimization model is proposed, along with defining a matching degree index. The first stage is the fault region identification stage, which uses the matching degree index to determine the suspicious fault region in order to reduce the search area. The second stage is used to identify the exact fault line and fault distance. A method to determine optimal PMU placement is also proposed in this paper. Case studies verify that the proposed fault-location algorithm and optimal PMU placement scheme can locate faults in large transmission networks quickly and accurately without requiring fault-type classification or fault phase selection.
引用
收藏
页码:1644 / 1652
页数:9
相关论文
共 50 条
  • [1] Fault Location Method for μPMU-Based Distribution Networks
    Wang, Lei
    Niu, Lin
    Zhou, Fengyuan
    Gao, Zhanjun
    2021 8TH INTERNATIONAL FORUM ON ELECTRICAL ENGINEERING AND AUTOMATION, IFEEA, 2021, : 478 - 484
  • [2] A PMU-based Dynamic Fault Location Estimation for Transmission Lines
    He Wen
    He Zhengyou
    Mai Ruikun
    2010 ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), 2010,
  • [3] A WAMS/PMU-based fault location technique
    Wang, Chun
    Dou, Chun-Xia
    Li, Xin-Bin
    Jia, Qing-Quan
    ELECTRIC POWER SYSTEMS RESEARCH, 2007, 77 (08) : 936 - 945
  • [4] An Efficient PMU-Based Fault-Location Technique for Multiterminal Transmission Lines
    Jiang, Quanyuan
    Wang, Bo
    Li, Xingpeng
    IEEE TRANSACTIONS ON POWER DELIVERY, 2014, 29 (04) : 1675 - 1682
  • [5] Transmission Network Fault Location Using Sparse PMU Measurements
    Bo, Wang
    Jiang, Quanyuan
    Cao, Yijia
    2009 INTERNATIONAL CONFERENCE ON SUSTAINABLE POWER GENERATION AND SUPPLY, VOLS 1-4, 2009, : 543 - 548
  • [6] A new PMU-based fault location algorithm for three-terminal
    Shen Hong-yu
    Zhang Wen-jun
    Duan Yu-bo
    Xu Jian-jun
    ADVANCES IN CHEMICAL, MATERIAL AND METALLURGICAL ENGINEERING, PTS 1-5, 2013, 634-638 : 3925 - 3929
  • [7] PMU-based Fault Location Technique for Three-terminal Parallel Transmission Lines with Series Compensation
    Saber, Ahmed
    ELECTRIC POWER COMPONENTS AND SYSTEMS, 2020, 48 (4-5) : 410 - 422
  • [8] A new PMU-based fault location algorithm for series compensated lines
    Yu, CS
    Liu, CW
    Yu, SL
    Jiang, JA
    IEEE TRANSACTIONS ON POWER DELIVERY, 2002, 17 (01) : 33 - 46
  • [9] A Novel Algorithm to Determine Fault location in a Transmission Line Using PMU Measurements
    Venugopal, Mahesh
    Tiwari, Chandrakant
    2013 IEEE INTERNATIONAL CONFERENCE ON SMART INSTRUMENTATION, MEASUREMENT AND APPLICATIONS (ICSIMA 2013), 2013,
  • [10] PMU-Based fault location method for Three-terminal transmission lines with outage of one line branch
    Saber, Ahmed
    ELECTRIC POWER SYSTEMS RESEARCH, 2020, 182