Partial Discharge Characteristics and Development of Typical XLPE Power Cable Insulation Defects

被引:0
作者
Zhao, Xuefeng [1 ]
Pu, Lu [1 ]
Ju, Zeli [1 ]
Ren, Shuangzan [1 ]
Duan, Wei [1 ]
Wang, Jianhui [2 ]
机构
[1] State Grid Shaanxi Elect Power Res Inst, Xian, Peoples R China
[2] State Grid Tianjin Elect Power Co, Xian, Peoples R China
来源
2016 INTERNATIONAL CONFERENCE ON CONDITION MONITORING AND DIAGNOSIS (CMD) | 2016年
关键词
partial discharge; PRPD pattern; statistical analysis; typical defect; XLPE;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
It is well known that preventive tests have been widely used as an important means to ensure reliable operation of the power cable. Nevertheless, in the early stages of insulation deterioration, the traditional preventive tests cannot effectively detect the faint abnormal signals caused by defects. As insulation failure usually starts with PD activities, which is not only one of the primary reasons to cause the insulation deterioration of the cable, but also the characteristic scalar to describe the insulation state of cable. Therefore, PD diagnosis is recommended by IEC, IEEE and CIGRE as an effective method to evaluate the properties of cable insulation condition. In order to study the PD characteristics of the typical defects in XLPE(Cross-Linked Polyethylene) power cable, two PD models as protrusion defect of cable joint and void defect in main insulation were designed, and then the PD measurement and analysis system based on the PDBase was established. The PD characteristics of typical defects were detected and compared, also the effects of the applied voltage on the phase-resolved PD (PRPD) pattern, waveform characteristic, discharge frequency, center-phase distribution and statistical features were investigated. The experimental results indicated that it has the high stability and repeatability of the discharge on the identical defect model under the same condition. The discharge development process, PRPD patterns, time domain waveforms, central phase changing of PD signals and statistical features had very similar distribution characteristics and those of different defect had different ones. So it provides a test basis for the pattern recognition of PD types and a deeper study on the PD mechanism of XPLE cable.
引用
收藏
页码:623 / 626
页数:4
相关论文
共 10 条
[1]   Fundamentals of partial discharge in the context of field cable testing [J].
Boggs, S ;
Densley, J .
IEEE ELECTRICAL INSULATION MAGAZINE, 2000, 16 (05) :13-18
[2]   Understanding electrical trees in solids: From experiment to theory [J].
Dissado, LA .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2002, 9 (04) :483-497
[3]   Condition assessment of power cable accessories using advanced VHF/UHF PD detection [J].
Meijer, Sander ;
Agoris, Pantelis D. ;
Gulski, Edward ;
Seitz, Paul P. ;
Hermans, Theo J. W. H. ;
Lamballais, Lawrence .
CONFERENCE RECORD OF THE 2006 IEEE INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATION, 2006, :482-+
[4]  
Phung B. T., 1999, Eleventh International Symposium on High Voltage Engineering (Conf. Publ. No.467), P328
[5]  
Qiu Chang-rong, 1994, PARTIAL DISCHARGE ME
[6]   Trends in partial discharge pattern classification: A survey [J].
Sahoo, NC ;
Salama, MMA ;
Bartnikas, R .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2005, 12 (02) :248-264
[7]  
Tamus Z. A., 2009, IEEE EL I C MONTR QC
[8]  
Uchida K, 1996, IEEE T PWRD, V2, P668
[9]  
WANG CC, 2006, ON LINE MONITORING D
[10]  
Wang Wei, 2011, XLPE INSULATED CABLE