Analysis of discharge energy on surge arrester configurations in 132 kV double circuit transmission lines

被引:7
|
作者
Hassan, Nor Hidayah Nor [1 ]
Abu Bakar, Ab Halim [2 ]
Illias, Hazlee Azil [1 ]
Abd Halim, Syahirah [1 ,4 ]
Mokhlis, Hazlie [1 ]
Terzija, Vladimir [3 ]
机构
[1] Univ Malaya, Fac Engn, Dept Elect Engn, Kuala Lumpur 50603, Malaysia
[2] Univ Malaya, Wisma R&D, UM Power Energy Dedicated Adv Ctr, Level 4,Jln Pantai Baharu, Kuala Lumpur 59990, Malaysia
[3] Univ Manchester, Sch Elect & Elect Engn, Manchester M13 9PL, Lancs, England
[4] Univ Kebangsaan Malaysia, Ctr Integrated Engn Syst & Adv Technol, Bangi, Malaysia
关键词
Transmission lines; Surge arrester; Lightning phenomena; Overvoltage; Discharge; TOWER;
D O I
10.1016/j.measurement.2019.02.088
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
Surge arrester has been proven to be the most effective application to provide optimum lightning protection for the transmission line. Thus, many works on optimizing lightning protection for transmission line have been conducted since the past. However, works on minimizing double circuit outages and surge arrester physical properties during transient overvoltages are less likely to be found. Therefore, in this work, several surge arrester configurations installed on a 132 kV double circuit transmission line were modelled using EMTP-RV to investigate their capability to withstand current and energy discharged by lightning strokes during back flashover phenomena. These configurations were then compared to determine the most effective protection design based on the actual tripping pattern recorded by the lightning detection system (LDS) in Malaysia. The selection was made by considering arresters' discharge energy due to variation in tower footing resistance, current magnitude, power frequency voltage, lightning tail time and front time, number of towers and span length. It was found that double circuit transmission line tripping can be completely eliminated by installing surge arresters at each phase conductor of one circuit. The selected arresters configuration provides sufficient lightning protection to the transmission line and complies with the discharge energy capability requirement specified by the utility company in Malaysia, of 5.1 kJ/kV for maximum continuous operating voltage (MCOV). (C) 2019 Elsevier Ltd. All rights reserved.
引用
收藏
页码:103 / 111
页数:9
相关论文
共 50 条
  • [41] Analysis on secondary stress for steel-tube tower of 1000 kV double circuit transmission lines on same tower
    Li, Mao-Hua
    Yang, Jing-Bo
    Li, Zheng-Liang
    Han, Jun-Ke
    Li, Feng
    Dianwang Jishu/Power System Technology, 2010, 34 (02): : 20 - 23
  • [42] Analysis of Safety Protection Measures for Maintenance Work of 500 kV Double-Circuit Transmission Lines on Same Tower
    Yang, Qi
    Zou, Dehua
    Zhang, Jianjun
    Li, Hui
    Chen, Jianping
    Li, Jinliang
    2017 2ND ASIA CONFERENCE ON POWER AND ELECTRICAL ENGINEERING (ACPEE 2017), 2017, 199
  • [43] Potential Distribution Analysis of Y-type Insulators in UHV 1000kV Double Circuit Transmission Lines
    Liao, Jintao
    Peng, Zongren
    Wang, Qingyu
    2015 IEEE 11TH INTERNATIONAL CONFERENCE ON THE PROPERTIES AND APPLICATIONS OF DIELECTRIC MATERIALS, 2015, : 576 - 579
  • [44] Application of 800-kV SF6 dead tank circuit breaker with transmission line surge arrester to control switching transient overvoltages
    Musa, YI
    Keri, AJF
    Halladay, JA
    Jagtiani, AS
    Mandeville, JD
    Johnnerfelt, B
    Stenström, L
    Khan, H
    Freeman, WB
    IEEE TRANSACTIONS ON POWER DELIVERY, 2002, 17 (04) : 957 - 962
  • [45] Electric Field Computation and Optimization of Composite Tower in 330 kV Double Circuit Transmission Lines
    Wang, Qingyu
    Peng, Zongren
    Yang, Xi
    Li, Naiyi
    Wang, Jialong
    Liao, Jintao
    2014 IEEE CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA (CEIDP), 2014, : 283 - 286
  • [46] Study on the Electromagnetic Environment of 1000 kV AC Double-Circuit Transmission Lines in China
    Huang, Daochun
    Ruan, Jiangjun
    Huo, Feng
    2009 IEEE/PES POWER SYSTEMS CONFERENCE AND EXPOSITION, VOLS 1-3, 2009, : 1143 - +
  • [47] Estimation of shielding failure number of different configurations of double-circuit transmission lines using leader progression analysis model
    M. Yahyaabadi
    B. Vahidi
    M. R. Bank Tavakoli
    Electrical Engineering, 2010, 92 : 79 - 85
  • [48] Estimation of shielding failure number of different configurations of double-circuit transmission lines using leader progression analysis model
    Yahyaabadi, M.
    Vahidi, B.
    Tavakoli, M. R. Bank
    ELECTRICAL ENGINEERING, 2010, 92 (02) : 79 - 85
  • [49] Research on electromagnetic environment of ±800 kV and ±500 kV double-circuit DC transmission lines on the same tower
    Wu, Gaobo
    Li, Jian
    Chen, Yuan
    Luo, Chujun
    Wang, Rusong
    Lin, Fang
    Dianwang Jishu/Power System Technology, 2015, 39 (09): : 2532 - 2538
  • [50] Lightning Surge Response of a Double-Circuit Transmission Tower with Incoming Lines to a Substation through FDTD Simulation
    Takami, Jun
    Tsuboi, Toshihiro
    Yamamoto, Keisuke
    Okabe, Shigemitsu
    Baba, Yoshihiro
    Ametani, Akihiro
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2014, 21 (01) : 96 - 104