Analysis of discharge energy on surge arrester configurations in 132 kV double circuit transmission lines

被引:7
|
作者
Hassan, Nor Hidayah Nor [1 ]
Abu Bakar, Ab Halim [2 ]
Illias, Hazlee Azil [1 ]
Abd Halim, Syahirah [1 ,4 ]
Mokhlis, Hazlie [1 ]
Terzija, Vladimir [3 ]
机构
[1] Univ Malaya, Fac Engn, Dept Elect Engn, Kuala Lumpur 50603, Malaysia
[2] Univ Malaya, Wisma R&D, UM Power Energy Dedicated Adv Ctr, Level 4,Jln Pantai Baharu, Kuala Lumpur 59990, Malaysia
[3] Univ Manchester, Sch Elect & Elect Engn, Manchester M13 9PL, Lancs, England
[4] Univ Kebangsaan Malaysia, Ctr Integrated Engn Syst & Adv Technol, Bangi, Malaysia
关键词
Transmission lines; Surge arrester; Lightning phenomena; Overvoltage; Discharge; TOWER;
D O I
10.1016/j.measurement.2019.02.088
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
Surge arrester has been proven to be the most effective application to provide optimum lightning protection for the transmission line. Thus, many works on optimizing lightning protection for transmission line have been conducted since the past. However, works on minimizing double circuit outages and surge arrester physical properties during transient overvoltages are less likely to be found. Therefore, in this work, several surge arrester configurations installed on a 132 kV double circuit transmission line were modelled using EMTP-RV to investigate their capability to withstand current and energy discharged by lightning strokes during back flashover phenomena. These configurations were then compared to determine the most effective protection design based on the actual tripping pattern recorded by the lightning detection system (LDS) in Malaysia. The selection was made by considering arresters' discharge energy due to variation in tower footing resistance, current magnitude, power frequency voltage, lightning tail time and front time, number of towers and span length. It was found that double circuit transmission line tripping can be completely eliminated by installing surge arresters at each phase conductor of one circuit. The selected arresters configuration provides sufficient lightning protection to the transmission line and complies with the discharge energy capability requirement specified by the utility company in Malaysia, of 5.1 kJ/kV for maximum continuous operating voltage (MCOV). (C) 2019 Elsevier Ltd. All rights reserved.
引用
收藏
页码:103 / 111
页数:9
相关论文
共 50 条
  • [1] Modeling and simulation of a metal oxide lightning surge arrester for 132kV overhead transmission lines
    Khan, Aziz Ullah
    European Journal of Electrical Engineering, 2020, 22 (4-5) : 389 - 394
  • [2] Modelling 132 kV substation for surge arrester studies
    Universiti Putra Malaysia
    Int. J. Emerg. Electr. Power Syst., 2008, 5
  • [3] Modelling 132 kV Substation for Surge Arrester Studies
    Ab Kadir, Mohd Zainal Abidin
    Ariff, Hatta Mohamed
    Azmi, Aida Maria
    INTERNATIONAL JOURNAL OF EMERGING ELECTRIC POWER SYSTEMS, 2008, 9 (05):
  • [4] Experience and long term performance of 132kV overhead lines gapless-type surge arrester
    Rawi, Iryani Mohamed
    Yahaya, Mohd Pauzi
    Ab Kadir, M. Z. A.
    Azis, Norhafiz
    2014 INTERNATIONAL CONFERENCE ON LIGHTNING PROTECTION (ICLP), 2014, : 517 - 520
  • [5] Parameters Affecting Lightning Backflash Over Pattern at 132kV Double Circuit Transmission Lines
    Abu Talib, Dian Najihah
    Abu Bakar, Ab. Halim
    Mokhlis, Hazlie
    2012 IEEE INTERNATIONAL CONFERENCE ON POWER AND ENERGY (PECON), 2012, : 808 - 812
  • [6] Analysis of Arrester Energy for 132kV Overhead Transmission Line due to Back Flashover and Shielding Failure
    Abu Bakar, Ab Halim
    Mokhlis, Hazlie
    Abd Halim, Syahirah
    Isa, Siti Sarah Mat
    Illias, Hazlee Azil
    2012 ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), 2012,
  • [7] Analysis of Arrester Energy for 132kV Overhead Transmission Line due to Back Flashover and Shielding Failure
    Hassan, Nor Hidayah Nor
    Abu Bakar, Ab Halim
    Mokhlis, Hazlie
    Illias, Hazlee Azil
    2012 IEEE INTERNATIONAL CONFERENCE ON POWER AND ENERGY (PECON), 2012, : 683 - 688
  • [9] Determination of surge arrester discharge energy using finite element analysis method
    Illias, Hazlee Azil
    Abd Halim, Syahirah
    Abu Bakar, Ab Halim
    Mokhlis, Hazlie
    IET SCIENCE MEASUREMENT & TECHNOLOGY, 2015, 9 (06) : 693 - 701
  • [10] Application of line surge arresters to double-circuit transmission lines
    Institute of Industrial Science, University of Tokyo, Tokyo, Japan
    不详
    Int. Symp. Light. Prot., XI SIPDA, 2011, (312-318):