Experimental study on frost growth and dynamic performance of air source heat pump system

被引:134
作者
Guo, Xian-Min [1 ,2 ]
Chen, Yi-Guang [2 ]
Wang, Wei-Hua [2 ]
Chen, Chun-Zheng [1 ]
机构
[1] Xian Jiaotong Univ, Xian 710049, Peoples R China
[2] Tianjin Univ Commerce, Sch Mech Engn, Tianjin 300134, Peoples R China
关键词
Air source heat pump; Frosting; Dynamic performance; Frost growth; Frost thickness; Experiment;
D O I
10.1016/j.applthermaleng.2008.01.007
中图分类号
O414.1 [热力学];
学科分类号
摘要
The effect of the frost growth and frost morphology on the performance of an air source heat pump was investigated experimentally. The frost thickness. frost accumulation and the dynamic performance of the heat PUMP were measured. It is found that the frost growth can be divided into three stages according to the frost morphology. In the initial stage, condensed water freezes and forms a transparent thin ice layer on the fins and tubes firstly, then the granular ices appear and grow gradually on the ice layer, and the column-shaped ice crystals are formed at last. The growth rate of the frost thickness, the heating capacity and COP of the heat pump increase with the frosting time significantly until the column-shaped frost layer is formed. In the second stage, the column-shaped ice crystals grow in its radius rather than in its length, and the frost thickness growth rate decreases or remains to be constant. However, the heating capacity and COP of the heat pump are only slightly affected by frosting on the outdoor coils. In the third stage, the ice crystals mainly grow in its length, and become gradually of all acerose-shaped one, finally a fluffy frost layer is formed. The frost thickness growth rate is about 2-4 times of that in the second stage. The drops per minute in the heating capacity and COP are increased by several times of those in the second stage. In additions it is found that the frost growth rate and the drop in the performance of the heat pump are highest when the outdoor air temperature is about 0 degrees C with various relative humidity. The experimental results are in agreement with the corresponding simulation data except in the third frosting stage. (C) 2008 Elsevier Ltd. All results reserved.
引用
收藏
页码:2267 / 2278
页数:12
相关论文
共 18 条
[1]   Fan supplied heat exchanger fin performance under frosting conditions [J].
Chen, H ;
Thomas, L ;
Besant, RW .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2003, 26 (01) :140-149
[2]  
CHEN YG, 2005, P 5 INT C COMPR REFR, V8, P373
[3]   Experimental investigation on the performance of air cooler under frosting conditions [J].
Deng, DQ ;
Xu, L ;
Xu, SQ .
APPLIED THERMAL ENGINEERING, 2003, 23 (07) :905-912
[4]  
Guo Xianmin, 2006, Journal of Xi'an Jiaotong University, V40, P544
[5]   PERFORMANCE OF FINNED-TUBE HEAT-EXCHANGERS UNDER FROSTING CONDITIONS .2. COMPARISON OF EXPERIMENTAL-DATA WITH MODEL [J].
KONDEPUDI, SN ;
ONEAL, DL .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 1993, 16 (03) :181-184
[6]   EFFECT OF FROST GROWTH ON THE PERFORMANCE OF LOUVERED FINNED TUBE HEAT-EXCHANGERS [J].
KONDEPUDI, SN ;
ONEAL, DL .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 1989, 12 (03) :151-158
[7]  
MILLER WA, 1987, ASHRAE T, V93, P1474
[8]   Local variation of frost layer thickness and morphology [J].
Qu, KY ;
Komori, S ;
Jiang, Y .
INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2006, 45 (02) :116-123
[9]   Frost formation on fin-and-tube heat exchangers. Part I - Modeling of frost formation on fin-and-tube heat exchangers [J].
Seker, D ;
Karatas, H ;
Egrican, N .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2004, 27 (04) :367-374
[10]   Frost formation on fin-and-tube heat exchangers. Part II - Experimental investigation of frost formation on fin-and-tube heat exchangers [J].
Seker, D ;
Karatas, H ;
Egrican, N .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2004, 27 (04) :375-377