The adaptive unit transverse differential protection based on the fault contributed current

被引:0
|
作者
Tai NengLing [1 ]
Wang Bo [1 ]
机构
[1] Shanghai Jiao Tong Univ, Dept Elect Power Engn, Shanghai 200030, Peoples R China
来源
关键词
generator internal fault; generator external fault; the unit transverse differential protection; the fault contributed current; adaptive protection;
D O I
10.1002/etep.203
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
A new adaptive unit transverse differential protection based on the fault contributed zero-sequence current for the generator is introduced in this paper. The performance of the conventional unit transverse differential protection is usually greatly affected by the unbalanced Current. To overcome this disadvantage. the fault contributed zero-sequence current is applied to remove the influence of the pre-fault Current. At the same time. analysis results show that the unbalanced Current always present the linear relationship with the stator current. According to that, the proposed scheme can change the setting Value adaptively, Which improves the protection sensitivity for the generator light internal fault. For the external fault. the scheme can enhance the protection reliability because it ensures a high restraint current. The new scheme is developed and the practical implementation of the protection equipment is also demonstrated. The test results show that the proposed approach is Successful in detecting the generator internal fault, and Could have high sensitivity and selectivity. Copyright (C) 2007 John Wiley & Sons, Ltd.
引用
收藏
页码:742 / 752
页数:11
相关论文
共 50 条
  • [1] Differential current-based fault protection with adaptive threshold for multiple PV-based DC microgrid
    Dhar, Snehamoy
    Dash, Pradipta Kishore
    IET RENEWABLE POWER GENERATION, 2017, 11 (06) : 778 - 790
  • [2] Phase correlation current differential protection based on fault component
    Li, Bin
    Zeng, Hongyan
    Fan, Ruiqing
    Bo, Zhiqian
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2011, 35 (03): : 54 - 58
  • [3] Sampling value based adaptive differential current protection of transformers
    Hu, Y.
    Chen, D.
    Yin, X.
    Zhang, Z.
    Dianli Xitong Zidonghue/Automation of Electric Power Systems, 2001, 25 (10): : 31 - 34
  • [4] Design of microprocessor-based transverse differential current directional protection device
    Chen, YL
    Bin, S
    Xu, QL
    Xiang, XZ
    2004 International Conference on Power System Technology - POWERCON, Vols 1 and 2, 2004, : 1391 - 1394
  • [5] An adaptive fault-component-based current differential protection scheme for distribution networks with inverter-based distributed generators
    Li, Haifeng
    Deng, Chengjiang
    Zhang, Zhenggang
    Liang, Yuansheng
    Wang, Gang
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2021, 128
  • [6] A CT break identifying method based on fault characteristics in current differential protection
    Yu Yue
    Liu Huanzhang
    Wang Xingguo
    Zhan Rongrong
    2017 2ND INTERNATIONAL SEMINAR ON ADVANCES IN MATERIALS SCIENCE AND ENGINEERING, 2017, 231
  • [7] A New Transmission Line Differential Protection based on Fault current DC Transients
    Latha, Adharapurapu Hema
    Bhimasingu, Ravikumar
    Katta, Sobhan Babu
    2018 IEEE 8TH POWER INDIA INTERNATIONAL CONFERENCE (PIICON), 2018,
  • [8] Protection scheme for VSC-HVDC transmission lines based on transverse differential current
    Li, Shilong
    Chen, Wei
    Yin, Xianggen
    Chen, Deshu
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2017, 11 (11) : 2805 - 2813
  • [9] A new digital directional transverse differential, current protection technique
    Eissa, MM
    Malik, OP
    IEEE TRANSACTIONS ON POWER DELIVERY, 1996, 11 (03) : 1285 - 1291
  • [10] Improved Transverse Current Differential Protection Resistant to Power Swing
    J. Ganeswara Rao
    Ashok Kumar Pradhan