Numerical investigation of the thermal and ventilation performance of a combined impinging jet ventilation and passive chilled beam system

被引:10
|
作者
Hu, Jun [1 ]
Kang, Yanming [1 ]
Lu, Yihang [1 ]
Yu, Jia [2 ]
Li, He [3 ]
Zhong, Ke [1 ]
机构
[1] Donghua Univ, Sch Environm Sci & Engn, Shanghai 201620, Peoples R China
[2] Yangzhou Univ, Sch Elect Energy & Power Engn, Yangzhou 225100, Peoples R China
[3] Univ Shanghai Sci & Technol, Sch Environm & Architecture, Shanghai 200093, Peoples R China
基金
中国国家自然科学基金;
关键词
Impinging jet ventilation; Passive chilled beam; Combined system; Ventilation performance; Thermal length scale; ENERGY-CONSUMPTION; DISPLACEMENT VENTILATION; MIXING VENTILATION; OFFICE; PREDICTION; BEHAVIOR; COMFORT; ROOMS; FLOW;
D O I
10.1016/j.buildenv.2022.109726
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Impinging jet ventilation (IJV) systems provide high ventilation efficiency and good indoor air quality (IAQ) in the cooling mode. However, they have a limited cooling capacity. Passive chilled beam (PCB) systems are widely used in indoor environments with high cooling loads and can potentially address the limitation of low cooling capacity of IJV. In this study, the possibility of combining IJV and PCB systems is investigated using computa-tional fluid dynamics (CFD) simulations. The effects of two main factors, namely the percentage of cooling load removed by the PCB system (eta) and supply air parameters (Lm) of the IJV system, on the thermal and ventilation performance of the IJV-PCB system are examined. The results indicate that the PCB system enhances the mixing of indoor air and effectively reduces the vertical temperature gradient in the IJV room. An optimal range of eta that improves the cooling capacity and maintains the high ventilation performance of IJV is determined. This range for an IJV-PCB system is 0.15 < eta < 0.45, considering thermal comfort, IAQ, and energy saving potential. In addition, the IJV-PCB system offers a wide selection range for Lm (0.4-1.2) compared with that of the IJV, and a high ventilation efficiency and good IAQ are maintained in the room in this range.
引用
收藏
页数:14
相关论文
共 50 条
  • [1] Numerical investigation of the thermal and ventilation performance of a combined impinging jet ventilation and passive chilled beam system
    Hu, Jun
    Kang, Yanming
    Lu, Yihang
    Yu, Jia
    Li, He
    Zhong, Ke
    Building and Environment, 2022, 226
  • [2] Thermal and ventilation performance of combined passive chilled beam and displacement ventilation systems
    Shan, Wenyu
    Rim, Donghyun
    ENERGY AND BUILDINGS, 2018, 158 : 466 - 475
  • [3] Numerical Evaluation of Thermal and Ventilation Performance of Combined Passive Chilled Beam-Displacement Ventilation Systems
    Shan, Wenyu
    Rim, Donghyun
    2017 ASHRAE WINTER CONFERENCE PAPERS, 2017,
  • [4] Numerical investigation of impinging jet ventilation in ICUs: Is thermal stratification a problem?
    Wang, Lei
    Wang, Zhiqiang
    Zhu, Sirui
    Zhu, Zhe
    Jin, Tao
    Wei, Jianjian
    BUILDING SIMULATION, 2023, 16 (07) : 1173 - 1185
  • [5] Numerical investigation of impinging jet ventilation in ICUs: Is thermal stratification a problem?
    Lei Wang
    Zhiqiang Wang
    Sirui Zhu
    Zhe Zhu
    Tao Jin
    Jianjian Wei
    Building Simulation, 2023, 16 : 1173 - 1185
  • [6] Performance evaluation of ductless personalized ventilation combined with impinging jet ventilation
    Yang, Bin
    Liu, Pengju
    Liu, Yihang
    Wang, Faming
    APPLIED THERMAL ENGINEERING, 2023, 222
  • [7] Numerical study on thermal stratification for impinging jet ventilation system in office buildings
    Hu, Jun
    Kang, Yanming
    Yu, Jia
    Zhong, Ke
    Building and Environment, 2021, 196
  • [8] Numerical study on thermal stratification for impinging jet ventilation system in office buildings
    Hu, Jun
    Kang, Yanming
    Yu, Jia
    Zhong, Ke
    BUILDING AND ENVIRONMENT, 2021, 196
  • [9] Optimization and operation control for the combined impinging jet ventilation and chilled ceiling system with different cooling loads
    Ye, Xiao
    Xi, Wentao
    Qi, Hechuang
    Zhou, Tianjun
    Gao, Yanfeng
    Kang, Yanming
    Zhong, Ke
    BUILDING AND ENVIRONMENT, 2023, 242
  • [10] Experimental comparison of thermal conditions in office rooms: Diffuse ceiling ventilation, chilled beam system, and chilled ceiling combined with mixing ventilation
    Lestinen, Sami
    Mustakallio, Panu
    Kilpelainen, Simo
    Kosonen, Risto
    Jokisalo, Juha
    Koskela, Hannu
    Melikov, Arsen Krikor
    SCIENCE AND TECHNOLOGY FOR THE BUILT ENVIRONMENT, 2020, 26 (05) : 631 - 642