High Impedance Fault Identification Method of Distribution Networks

被引:0
|
作者
Huang, Yong [1 ]
Chen, Minyou [1 ]
Zhai, Jinqian [1 ]
Yan, Hong [2 ]
机构
[1] Chongqing Univ, State Key Lab Power Transmiss Equipment & Syst Se, Chongqing 400044, Peoples R China
[2] AnHui Elect Power Corp, NingGuo Elect Power Supply Co LTD, Xuan Cheng 242300, Peoples R China
来源
ELECTRICAL POWER & ENERGY SYSTEMS, PTS 1 AND 2 | 2012年 / 516-517卷
基金
中国国家自然科学基金;
关键词
high-impedance fault; Discrete Wavelet Transform; Distribution networks; fault mode; Transients signal;
D O I
10.4028/www.scientific.net/AMR.516-517.1785
中图分类号
O414.1 [热力学];
学科分类号
摘要
High impedance fault has always been difficult for distribution network fault identification due to its unobvious fault signature and difficult detection. This paper decomposed the transient signal in multi-scale by utilizing the good localization performance of the wavelet in both time domain and frequency domain, reconstructed the wavelet coefficients under each scale, took the wavelet reconstruction coefficient which was under the scale 3, calculated the size spectrum of each feeder line in timing floating window and identified the circuits in which the faults lined according to the value of the size spectrum. The high impedance fault simulation system was built based upon the study of the various transient signals in power systems, and the high impedance fault simulation analysis of the distribution feeder was undertaken through PSCAD simulation platform using high impedance fault model. Simulation analysis showed that the method could effectively extract the feature of high impedance fault on high impedance fault identification.
引用
收藏
页码:1785 / +
页数:2
相关论文
共 50 条
  • [31] Detection of High Impedance Fault in Power Distribution Systems Using Mathematical Morphology
    Gautam, Suresh
    Brahma, Sukumar M.
    IEEE TRANSACTIONS ON POWER SYSTEMS, 2013, 28 (02) : 1226 - 1234
  • [32] Fault Location in Double Circuit Medium Power Distribution Networks Using an Impedance-Based Method
    Dashti, Rahman
    Salehizadeh, Seyed Mehdi
    Shaker, Hamid Reza
    Tahavori, Maryamsadat
    APPLIED SCIENCES-BASEL, 2018, 8 (07):
  • [33] High impedance fault detection method in distribution network based on improved Emanuel model and DenseNet
    Bai Hao
    Tang Bingnan
    Cheng Tianyu
    Liu Hongwen
    ENERGY REPORTS, 2022, 8 : 982 - 987
  • [34] Adaptive Kalman filter and neural network based high impedance fault detection in power distribution networks
    Samantaray, S. R.
    Dash, P. K.
    Upadhyay, S. K.
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2009, 31 (04) : 167 - 172
  • [35] High Impedance Fault Detection in Distribution Networks Using Support Vector Machines Based on Wavelet Transform
    Sarlak, M.
    Shahrtash, S. M.
    2008 IEEE ELECTRICAL POWER AND ENERGY CONFERENCE, 2008, : 529 - 534
  • [36] A Feature Selection Method for High Impedance Fault Detection
    Cui, Qiushi
    El-Arroudi, Khalil
    Weng, Yang
    IEEE TRANSACTIONS ON POWER DELIVERY, 2019, 34 (03) : 1203 - 1215
  • [37] High impedance fault detection and identification based on pattern recognition of phase displacement computation
    Ali, Mohd Syukri
    Abu Bakar, Ab Halim
    Tan, Chia Kwang
    Arof, Hamzah
    Mokhlis, Hazlie
    IEEJ TRANSACTIONS ON ELECTRICAL AND ELECTRONIC ENGINEERING, 2018, 13 (04) : 549 - 560
  • [38] Fault Detection of Distribution Network Considering High Impedance Faults
    Liu S.
    Liu H.
    Bi T.
    Yu X.
    Jiang Y.
    Dianwang Jishu/Power System Technology, 2023, 47 (08): : 3438 - 3447
  • [39] A hybrid method for high impedance fault classification and detection
    Moloi, K.
    Jordaan, J. A.
    Hamam, Y.
    2019 SOUTHERN AFRICAN UNIVERSITIES POWER ENGINEERING CONFERENCE/ROBOTICS AND MECHATRONICS/PATTERN RECOGNITION ASSOCIATION OF SOUTH AFRICA (SAUPEC/ROBMECH/PRASA), 2019, : 548 - 552
  • [40] Fault Distance Estimation in Distribution Network for high impedance faults
    Dasco, Antony
    Marguet, Raphael
    Raison, Bertrand
    2015 IEEE EINDHOVEN POWERTECH, 2015,