Field experiences with measurements of dielectric response in frequency domain for power transformer diagnostics

被引:96
|
作者
Blennow, J [1 ]
Ekanayake, C
Walczak, K
García, B
Gubanski, SM
机构
[1] Chalmers Univ Technol, Dept Elect Power Engn, S-41296 Gothenburg, Sweden
[2] Poznan Univ Tech, Elect Power Res Inst, PL-61419 Poznan, Poland
[3] Univ Carlos III Madrid, Dept Elect Engn, Madrid 28911, Spain
关键词
field measurements; frequency domain spectroscopy; oil-paper insulation; transformer diagnostics; water content;
D O I
10.1109/TPWRD.2005.861231
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Some new methods, based on characterization of the dielectric response of transformer insulation in time and frequency domains, have been pointed out by CIGRE as suitable to assess moisture content in pressboard and paper. Measuring devices available today on the market are quite robust in field conditions; however there is a risk that undesired internal and external factors might influence the measurements. These influences can lead to mistaken interpretation of insulation wetness. Operators should therefore be aware of the risks appearing at different measuring conditions and of the precautions that can be taken to minimize their effects. This work presents a systematic investigation oil the influence of some factors on file results of dielectric response measurements in field conditions. The errors that can be committed during the measurements if certain precautions are not taken, with different equipment connected in parallel, are evaluated. The influence of rain and electromagnetic disturbances are also analyzed proposing solutions to attenuate their effects. Finally, a discussion on the influence of temperature distribution follows. The work is concentrated on frequency response measurements, although some results from the use of polarization and depolarization current technique are also discussed.
引用
收藏
页码:681 / 688
页数:8
相关论文
共 50 条
  • [1] Experiences of dielectric response measurement in frequency domain for diagnostics of transformer insulation system
    Ramakichenan, V.
    Jain, Rahul Kumar
    Sethumadhavan, Thekkeveetil
    Chaudhari, Sushil E.
    Venkatasami, A.
    Chandle, Jayalakshmi
    PROCEEDINGS OF 2008 INTERNATIONAL CONFERENCE ON CONDITION MONITORING AND DIAGNOSIS, 2007, : 914 - +
  • [2] Experience with transformer diagnostics based on dielectric response measurements in time domain
    Kuzmin, Oleg
    Sautter, Dietrich
    Thummalacharla, Sairam
    PRZEGLAD ELEKTROTECHNICZNY, 2018, 94 (10): : 99 - 103
  • [3] Diagnostics of Transformer Insulation Based on Dielectric Response Measurements
    Jadav, Raj B.
    Saha, Tapan K.
    Ekanayake, Chandima
    2013 IEEE 1ST INTERNATIONAL CONFERENCE ON CONDITION ASSESSMENT TECHNIQUES IN ELECTRICAL SYSTEMS (CATCON), 2013, : 231 - 236
  • [4] Case Studies of Factors Influencing Frequency Response Analysis Measurements and Power Transformer Diagnostics
    Reykherdt, Andrey A.
    Davydov, Valery
    IEEE ELECTRICAL INSULATION MAGAZINE, 2011, 27 (01) : 22 - 30
  • [5] Frequency Domain Diagnostics of Transformer Insulation
    Gutten, M.
    Sebok, M.
    Korenciak, D.
    Brncal, P.
    Kubis, M.
    Zukowski, P.
    Koltunowicz, T. N.
    DEVICES AND METHODS OF MEASUREMENTS, 2019, 10 (04): : 353 - 359
  • [6] A Review of Frequency Response Analysis Methods for Power Transformer Diagnostics
    Alsuhaibani, Saleh
    Khan, Yasin
    Beroual, Abderrahmane
    Malik, Nazar Hussain
    ENERGIES, 2016, 9 (11)
  • [7] Dielectric spectroscopy in time and frequency domain applied to diagnostics of power transformers
    Gäfvert, U
    Adeen, L
    Tapper, M
    Ghasemi, P
    Jönsson, B
    PROCEEDINGS OF THE 6TH INTERNATIONAL CONFERENCE ON PROPERTIES AND APPLICATIONS OF DIELECTRIC MATERIALS, VOLS 1 & 2, 2000, : 825 - 830
  • [8] Using the Complex Values of the Frequency Response to Improve Power Transformer Diagnostics
    Samimi, M. H.
    Tenbohlen, S.
    Akmal, A. A. Shayegani
    Mohseni, H.
    2016 24TH IRANIAN CONFERENCE ON ELECTRICAL ENGINEERING (ICEE), 2016, : 1689 - 1693
  • [9] Diagnostics of Transformer Insulation by Frequency Domain Spectroscopy
    Gutten, Miroslav
    Korenciak, Daniel
    Brncal, Peter
    Cefer, Viktor
    PRZEGLAD ELEKTROTECHNICZNY, 2020, 96 (08): : 43 - 46
  • [10] Applicability of the Dielectric Response Methods of Diagnostics of Power Transformers Hungarian Experiences
    Nemeth, Balint
    Csepes, Gusztav
    Voeroes, Csaba
    2011 ELECTRICAL INSULATION CONFERENCE (EIC), 2011, : 49 - 53