A simplified analytical model for indirect evaporative cooling considering condensation from fresh air: Development and application

被引:80
作者
Chen, Yi [1 ]
Luo, Yimo [1 ]
Yang, Hongxing [1 ]
机构
[1] Hong Kong Polytech Univ, Dept Bldg Serv Engn, RERG, Hong Kong, Hong Kong, Peoples R China
关键词
IEC pre-cooling; Condensation; Modeling; Energy performance; HEAT-EXCHANGERS; PERFORMANCE; COOLER; FEASIBILITY; SIMULATION; CLIMATE; MASS; HOT;
D O I
10.1016/j.enbuild.2015.09.054
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
In a hybrid cooling system, an indirect evaporative cooling (IEC) unit is installed before an air handling unit to pre-cool the incoming fresh air, in order to reduce the energy consumption of the air-conditioning system. When the system is applied in humid regions, as the dew point temperature of the fresh air is higher, condensation will probably occur in the dry channels of IEC unit. However, the model of IEC unit considering condensation had been seldom studied, which would become an obstacle in predicting the performance of the hybrid system. In order to evaluate its energy saving potential precisely, the paper aims to establish a short-cut model for predicting the annual performance of the hybrid cooling system considering condensation in IEC unit. This paper firstly presents the analytical models for IEC under non-condensation, totally condensation and partially condensation states and proposed a method for judging the three states as well. The models were validated by the published data from literatures. The validated model was then incorporated with TRNSYS for predicting the performance of an IEC hybrid cooling system in a wet market in Hong Kong and the annual simulation results were validated by a field measurement with good agreement. (C) 2015 Elsevier B.V. All rights reserved.
引用
收藏
页码:387 / 400
页数:14
相关论文
共 26 条
[1]  
Alonso JFSJ, 1998, ENERG BUILDINGS, V29, P23
[2]  
[Anonymous], 1916, Z VER DTSCH
[3]   Potential of the evaporative cooling techniques in the Gulf region of the Kingdom of Saudi Arabia [J].
Bajwa, Maqsood ;
Aksugur Erdal ;
Al-Otaibi, Ghazi .
Renewable energy, 1993, 3 (01) :15-29
[4]  
Chen P. L., 1993, ASHRAE T 1, V99
[5]   Energy performance of air-conditioning systems using an indirect evaporative, cooling combined with a cooling/reheating treatment [J].
Cianfrini, Claudio ;
Corcione, Massimo ;
Habib, Emanuele ;
Quintino, Alessandro .
ENERGY AND BUILDINGS, 2014, 69 :490-497
[6]   Performance evaluation of an indirect pre-cooling evaporative heat exchanger operating in hot and humid climate [J].
Cui, X. ;
Chua, K. J. ;
Islam, M. R. ;
Ng, K. C. .
ENERGY CONVERSION AND MANAGEMENT, 2015, 102 :140-150
[7]   Numerical simulation of a novel energy-efficient dew-point evaporative air cooler [J].
Cui, X. ;
Chua, K. J. ;
Yang, W. M. .
APPLIED ENERGY, 2014, 136 :979-988
[8]   Studying the performance of an improved dew-point evaporative design for cooling application [J].
Cui, X. ;
Chua, K. J. ;
Yang, W. M. ;
Ng, K. C. ;
Thu, K. ;
Nguyen, V. T. .
APPLIED THERMAL ENGINEERING, 2014, 63 (02) :624-633
[9]   Energy saving potential of an indirect evaporative cooler as a pre-cooling unit for mechanical cooling systems in Iran [J].
Delfani, Shahram ;
Esmaeelian, Jafar ;
Pasdarshahri, Hadi ;
Karami, Maryam .
ENERGY AND BUILDINGS, 2010, 42 (11) :2169-2176
[10]   Heat and mass transfer analogy for condensation of humid air in a vertical channel [J].
Desrayaud, G ;
Lauriat, G .
HEAT AND MASS TRANSFER, 2001, 37 (01) :67-76