Primary Frequency Regulation by Deloaded Wind Turbines Using Variable Droop

被引:519
作者
Vidyanandan, K. V. [1 ]
Senroy, Nilanjan [2 ]
机构
[1] NTPC Ltd, Power Management Inst, Noida, Uttar Pradesh, India
[2] Indian Inst Technol, Dept Elect Engn, Delhi, India
关键词
Deloading; doubly-fed induction generator; droop; primary frequency regulation; wind turbine;
D O I
10.1109/TPWRS.2012.2208233
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper introduces a method to improve the primary frequency contribution of grid connected variable speed wind turbine generators (WTGs). Using their energy reserve margins, deloaded WTGs are controlled to provide relief to the grid during depressed frequency conditions. The frequency support from individual WTGs is regulated based on the available reserve, which depends on the prevailing wind velocities. By continuously adjusting the droop of the WTG in response to wind velocities, its primary frequency response is significantly improved in terms of reduced stresses on WTGs during low wind speeds. The impact of variable droop operation on two aspects of WTG operation is investigated-primary frequency contribution and smoothening power fluctuations caused due to changes in wind speed. Also highlighted is the usefulness of this control when adopted by wind farms.
引用
收藏
页码:837 / 846
页数:10
相关论文
共 32 条
[1]  
Ackermann T, 2005, WIND POWER IN POWER SYSTEMS, P1, DOI 10.1002/0470012684
[2]  
Anaya-Lara O., 2009, Wind Energy Generation : Modeling and Control
[3]  
[Anonymous], 2004, APP 1 LOAD FREQ CONT
[4]  
[Anonymous], O M DAT BOOK RIH SUP
[5]  
Baggini A., 2008, HDB POWER QUALITY
[6]   Energy Management in Autonomous Microgrid Using Stability-Constrained Droop Control of Inverters [J].
Barklund, E. ;
Pogaku, Nagaraju ;
Prodanovic, Milan ;
Hernandez-Aramburo, C. ;
Green, Tim C. .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2008, 23 (05) :2346-2352
[7]  
Central Electricity Regulatory Commission and Others, 2010, IND EL GRID COD
[8]   Enhancing Frequency Response Control by DFIGs in the High Wind Penetrated Power Systems [J].
Chang-Chien, Lee-Ren ;
Lin, Wei-Ting ;
Yin, Yao-Ching .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2011, 26 (02) :710-718
[9]   Participation of doubly fed induction wind generators in system frequency regulation [J].
de Almeida, Rogerio G. ;
Pecas Lopes, J. A. .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2007, 22 (03) :944-950
[10]   Comparison of the response of doubly fed and fixed-speed induction generator wind turbines to changes in network frequency [J].
Ekanayake, J ;
Jenkins, N .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 2004, 19 (04) :800-802