Ventilation and energy performance of partitioned indoor spaces under mixing and displacement ventilation

被引:55
作者
Ahn, Hyeunguk [1 ]
Rim, Donghyun [1 ]
Lo, L. James [2 ]
机构
[1] Penn State Univ, Dept Architectural Engn, University Pk, PA 16802 USA
[2] Drexel Univ, Dept Civil Architectural & Environm Engn, Philadelphia, PA 19104 USA
关键词
computational fluid dynamics; indoor partition; ventilation effectiveness; energy consumption; thermal comfort; draft risk; COMPUTATIONAL FLUID-DYNAMICS; AIR-DISTRIBUTION SYSTEMS; ROOM AIR; OFFICE ENVIRONMENT; TURBULENCE; LOCATION; QUALITY; FLOW; CFD; EFFICIENCY;
D O I
10.1007/s12273-017-0410-z
中图分类号
O414.1 [热力学];
学科分类号
摘要
Large variation in indoor air quality (IAQ) and thermal comfort can occur in partitioned office spaces due to heterogeneous air mixing. However, few published studies examined IAQ, thermal comfort, and energy performance of partitioned occupied spaces, which are commonly found in today's buildings. The objective of this study is to evaluate indoor environmental quality and air conditioning performance of a partitioned room under two typical ventilation modes: (1) mixing ventilation and (2) displacement ventilation. For a total of six representative air-conditioning scenarios, three-dimensional computational fluid dynamics (CFD) simulations are performed to examine temperature distribution, ventilation effectiveness, energy consumption, and local thermal comfort for two partitioned spaces. Simulation results indicate that temperature distribution in a partitioned room is a strong function of ventilation strategy (mixing vs. displacement), but marginally affected by diffuser arrangements. Local age-of-air (air freshness) significantly varies with both diffuser arrangement and ventilation strategy. Regarding energy consumption, displacement ventilation can achieve an indoor set-point temperature in the partitioned spaces about two times faster than mixing ventilation. Under mixing ventilation, the time to achieve a set-point temperature was notably reduced when each partitioned space is served by its own diffuser. For the same supply airflow rate, displacement ventilation can generate local draft risk at ankle level, while mixing ventilation may result in a draft sensation in wider areas around an occupant. Overall, the results suggest that mixing ventilation system can save energy if each partitioned zone is served by its own diffuser such as a multi-split air conditioning. However, when multiple partitioned zones are served by only one diffuser, displacement ventilation is more energy-efficient and can achieve higher ventilation effectiveness than mixing ventilation.
引用
收藏
页码:561 / 574
页数:14
相关论文
共 49 条
  • [1] Recent advances on the numerical modelling of turbulent flows
    Argyropoulos, C. D.
    Markatos, N. C.
    [J]. APPLIED MATHEMATICAL MODELLING, 2015, 39 (02) : 693 - 732
  • [2] ASHRAE, 2013, 552013 ASHRAE ANSIAS
  • [3] ASHRAE, 2007, 622007 ASHRAE ANSIAS
  • [4] Ashrae, 2009, ASHRAE Handbook: Fundamentals
  • [5] Awbi H.B., 2003, Ventilation of Buildings
  • [6] Energy efficient room air distribution
    Awbi, HB
    [J]. RENEWABLE ENERGY, 1998, 15 (1-4) : 293 - 299
  • [7] Procedure for estimation and reporting of uncertainty due to discretization in CFD applications
    Celik, Ishmail B.
    Ghia, Urmila
    Roache, Patrick J.
    Freitas, Christopher J.
    [J]. JOURNAL OF FLUIDS ENGINEERING-TRANSACTIONS OF THE ASME, 2008, 130 (07): : 0780011 - 0780014
  • [8] Numerical investigatipn of ventilation performance of different air supply devices in an office environment
    Chen, Huijuan
    Janbakhsh, Setareh
    Larsson, Ulf
    Moshfegh, Bahram
    [J]. BUILDING AND ENVIRONMENT, 2015, 90 : 37 - 50
  • [9] Chung, 1999, J BUILD PHYS, V22, P208, DOI DOI 10.1177/109719639902200305
  • [10] AIR TURBULENCE AND SENSATION OF DRAFT
    FANGER, PO
    MELIKOV, AK
    HANZAWA, H
    RING, J
    [J]. ENERGY AND BUILDINGS, 1988, 12 (01) : 21 - 39