Statistical Analysis of AC and DC Breakdown Voltage of JMEO (Jatropha Methyl Ester Oil), Mineral Oil and Their Mixtures

被引:0
作者
Sitorus, Henry B. H. [1 ]
Beroual, Abderrahmane [2 ]
Setiabudy, Rudy [3 ]
Bismo, Setijo [3 ]
机构
[1] Univ Lampung Unila, Engn Fac, Elect Engn Dept, Bandar Lampung, Indonesia
[2] Univ Lyon, Ampere CNRS, UMR 5005, Ecole Cent Lyon, 36 Ave Guy Collongue, F-69134 Ecully, France
[3] Univ Indonesia, Engn Fac, Depok, Indonesia
来源
2017 IEEE 19TH INTERNATIONAL CONFERENCE ON DIELECTRIC LIQUIDS (ICDL) | 2017年
关键词
Breakdown voltage; AC; DC; jatropha curcas methyl ester oil (JMEO); mineral oil (MO); JMEO/MO mixtures; breakdown voltage; statistical analysis;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper reports on a comparative study of statistical Breakdown Voltage (BDV) in a natural ester oil namely jatropha curcas methyl ester oil (JMEO) extracted from the fruit seeds of jatropha curcas plants, mineral oil (MO) and two JMEO/MO oil mixtures (namely (50%JMEO+50%MO) and (80%JMEO+20%MO)) using spherical electrode under DC and AC voltages. It is shown that the average AC breakdown voltage of JMEO is higher than that of mineral oil. Meanwhile it is similar under DC voltage. The statistical analysis shows that all large data groups (n>40) for AC and DC breakdown voltages of JMEO, MO and oil mixtures obey to the normal distribution law. This is proved using Shapiro-Wilk test, skewness and kurtosis values. It also observed that AC mean breakdown voltage of JMEO is higher than that of oils mixture (50%JMEO+50%MO) and MO, but it is similar with oils mixture (80%JMEO+20%MO). AC mean breakdown voltage of MO is the lowest one. DC mean breakdown voltages of JMEO, MO and oil mixtures (50%JMEO+50%MO) are similar. In contrast, DC mean breakdown voltage of oils mixture (80%JMEO+20%MO) is the highest one.
引用
收藏
页数:4
相关论文
共 8 条
[1]  
[Anonymous], 1995, 60156ED2 IEC
[2]   Comparative Study of Statistical Breakdown in Mineral, Synthetic and Natural Ester Oils under AC Voltage [J].
Dang, Viet-Hung ;
Beroual, A. ;
Perrier, C. .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2012, 19 (05) :1508-1513
[3]  
Hopkinson P., 2009, P IEEE POW EN SOC GE, P1
[4]   Vegetable oils for liquid-filled transformers [J].
Oommen, TV .
IEEE ELECTRICAL INSULATION MAGAZINE, 2002, 18 (01) :6-11
[5]  
Oommen TV, 2000, 2000 ANNUAL REPORT CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA, VOLS. I & II, P308, DOI 10.1109/CEIDP.2000.885288
[6]   Experimental investigations on different insulating liquids and mixtures for power transformers [J].
Perrier, C ;
Beroual, A ;
Bessede, JL .
CONFERENCE RECORD OF THE 2004 IEEE INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATION, 2004, :237-240
[7]  
SHAPIRO SS, 1965, BIOMETRIKA, V52, P591, DOI 10.2307/2333709
[8]   Jatropha Curcas Methyl Ester Oil Obtaining as Vegetable Insulating Oil [J].
Sitorus, Henry B. H. ;
Setiabudy, Rudy ;
Bismo, Setijo ;
Beroual, Abderrahmane .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2016, 23 (04) :2021-2028