Analysis of Arrester Energy for 132kV Overhead Transmission Line due to Back Flashover and Shielding Failure

被引:0
作者
Hassan, Nor Hidayah Nor [1 ]
Abu Bakar, Ab Halim [2 ]
Mokhlis, Hazlie [1 ]
Illias, Hazlee Azil [1 ]
机构
[1] Univ Malaya, Fac Engn, Dept Elect Engn, Kuala Lumpur 50603, Malaysia
[2] Univ Malaya, UM Power Energy Dedicated Adv Ctr UMPEDAC, Wisma R&D, Kuala Lumpur 59990, Malaysia
来源
2012 IEEE INTERNATIONAL CONFERENCE ON POWER AND ENERGY (PECON) | 2012年
关键词
Arrester; Back Flashover; Shielding Failure; Bergeron model; PSCAD/EMTDC;
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
This paper presents the analysis of lightning arrester energy due to back flashover and shielding failure phenomena in a 132kV transmission line in Malaysia. The transmission line, towers and surge arresters were modeled using PSCAD/EMTDC software. The model has been used to simulate the discharged energy from lightning arresters that were installed on the tower in the event of back flashover and shielding failure. The arrester was modeled based on the IEEE frequency dependent model. Comparison between the simulation results and values calculated theoretically was performed to validate the model that has been developed. The results show that both are in reasonable agreement with each other. The maximum calculated and simulated energy discharged by the arrester is found to be less than 5.1 kJ/kV, which is the rating of arresters installed in the actual 132kV transmission lines.
引用
收藏
页码:683 / 688
页数:6
相关论文
共 14 条
  • [1] A method of a lightning surge analysis recommended in Japan using EMTP
    Ametani, A
    Kawamura, T
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2005, 20 (02) : 867 - 875
  • [2] [Anonymous], 1985, IEEE T POWER AP SYST, V104, P919
  • [3] [Anonymous], 1999, 3311 CIGRE WG EL
  • [4] [Anonymous], 1991, 3301 CIGRE WG
  • [5] Bakar A.A., 2010, POW SYST TECHN POWER, P1
  • [6] Caulker D., 2010, 2010 6th International Conference on Electrical & Computer Engineering (ICECE 2010), P298, DOI 10.1109/ICELCE.2010.5700687
  • [7] TRAVEL TIME OF TRANSMISSION TOWERS
    CHISHOLM, WA
    CHOW, YL
    SRIVASTAVA, KD
    [J]. IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1985, 104 (10): : 2922 - 2928
  • [8] Hillman A. R., 1999, INSULATION COORDINAT
  • [9] IEEE Standard, IEEE GUID IMPR LIGHT, P1243
  • [10] IEEE WG 3.4.11, 1992, IEEE T POWER DELIVER, V7, P302