Power hardware in the loop validation of fault ride through of VSC HVDC connected offshore wind power plants

被引:34
作者
Sharma, Ranjan [1 ]
Wu, Qiuwei [2 ]
Cha, Seung Tae [2 ]
Jensen, Kim H. [1 ]
Rasmussen, Tonny W. [2 ]
Ostegaard, Jacob [2 ]
机构
[1] Siemens Wind Power AS, DK-7330 Brander, Denmark
[2] Tech Univ Denmark, Dept Elect Engn, Ctr Elect Power & Energy, DK-2800 Lyngby, Denmark
关键词
Fault ride through; High voltage DC (HVDC); Offshore wind power plant; Power hardware in the loop (PHIL); Voltage source converter (VSC); FARMS;
D O I
10.1007/s40565-014-0049-z
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents the power hardware in the loop (PHIL) validation of a feed forward DC voltage control scheme for the fault ride through (FRT) of voltage source converter (VSC) high voltage DC (HVDC) connected offshore wind power plants (WPPs). In the proposed FRT scheme, the WPP collector network AC voltage is actively controlled by considering both the DC voltage error and the AC current from the WPP AC collector system which ensures fast and robust FRT of the VSC HVDC connected offshore WPPs. The PHIL tests were carried out in order to verify the efficacy of the proposed feed forward DC voltage control scheme for enhancing the FRT capability of the VSC HVDC connected WPPs. The PHIL test results have demonstrated the proper control coordination between the offshore WPP and the WPP side VSC and the efficient FRT of the VSC HVDC connected WPPs.
引用
收藏
页码:23 / 29
页数:7
相关论文
共 17 条
  • [1] Ackermann T, 2005, WIND POWER IN POWER SYSTEMS, P1, DOI 10.1002/0470012684
  • [2] Simulated Onshore-Fault Ride Through of Offshore Wind Farms Connected Through VSC HVDC
    Arulampalam, A.
    Ramtharan, G.
    Caliao, N.
    Ekanayake, J.
    Jenkins, N.
    [J]. WIND ENGINEERING, 2008, 32 (02) : 103 - 113
  • [3] HVDC connection of offshore wind farms to the transmission system
    Bresesti, Paola
    Kling, Wil L.
    Hendriks, Ralph L.
    Vailati, Riccardo
    [J]. IEEE TRANSACTIONS ON ENERGY CONVERSION, 2007, 22 (01) : 37 - 43
  • [4] Enhanced Fault Ride-Through Method for Wind Farms Connected to the Grid Through VSC-Based HVDC Transmission
    Feltes, Christian
    Wrede, Holger
    Koch, Friedrich W.
    Erlich, Istvan
    [J]. IEEE TRANSACTIONS ON POWER SYSTEMS, 2009, 24 (03) : 1537 - 1546
  • [5] Jianbo Y., 2009, P 5 INT C WIR COMM N, P5, DOI [10.1109/WICOM.2009.5303767, DOI 10.1109/WICOM.2009.5303767]
  • [6] Offshore wind farm with centralised power conversion and DC interconnection
    Jovcic, D.
    Strachan, N.
    [J]. IET GENERATION TRANSMISSION & DISTRIBUTION, 2009, 3 (06) : 586 - 595
  • [7] Jovcic D, 2006, IEEE POWER ENG SOC, P1
  • [8] Loss evaluation of HVAC and HVDC transmission solutions for large offshore wind farms
    Negra, N. Barberis
    Todorovic, J.
    Ackermann, T.
    [J]. ELECTRIC POWER SYSTEMS RESEARCH, 2006, 76 (11) : 916 - 927
  • [9] Fault ride through of fully rated converter wind turbines with AC and DC transmission systems
    Ramtharan, G.
    Arulampalam, A.
    Ekanayake, J. B.
    Hughes, F. M.
    Jenkins, N.
    [J]. IET RENEWABLE POWER GENERATION, 2009, 3 (04) : 426 - 438
  • [10] Aggregated Wind Turbine Models for Power System Dynamic Studies
    Shafiu, A.
    Anaya-Lara, O.
    Bathurst, G.
    Jenkins, N.
    [J]. WIND ENGINEERING, 2006, 30 (03) : 171 - 185