First in situ operation performance test of ground source heat pump in Tunisia

被引:18
作者
Naili, Nabiha [1 ]
Attar, Issam [1 ]
Hazami, Majdi [1 ]
Farhat, Abdelhamid [1 ]
机构
[1] Ctr Rech & Technol Energie CRTEn, Lab Proc Therm LPT, Hammam Lif 2050, Tunisia
关键词
Ground source heat pump; Horizontal ground heat exchanger; Building cooling; Performance analysis; SYSTEM; OPTIMIZATION; EXCHANGERS; CONFIGURATIONS; CLIMATE; TURKEY; SOIL;
D O I
10.1016/j.enconman.2013.06.014
中图分类号
O414.1 [热力学];
学科分类号
摘要
The main purpose of this paper is to study the energetic potential of the deployment in Tunisia of the Ground Source Heat Pump (GSHP) system for cooling mode application. Therefore, a pilot GSHP system using horizontal Ground Heat Exchanger (GHE) was installed and experimented in the Research and Technology Center of Energy (CRTEn), Borj Cedria. The experiment is conducted in a test room with a floor area of about 12 m(2). In the floor of the tested room is integrated a polyethylene exchanger (PEX) used as a radiant floor cooling (RFC) system. The experimental setup mainly includes the ground temperature, the temperature and flow rate of water circulating in the heat pump and the GHE, as well as the power consumption of the heat pump and circulating pumps. These experimental data are essentially used to evaluate the coefficient of performance of the heat pump (COPhp) and the overall system (COPsys) for continuous operation mode. The COPhp and the COPsys were found to be 4.25 and 2.88, respectively. These results reveal that the use of the ground source heat pump is very appropriate for Tunisian building cooling. (C) 2013 Elsevier Ltd. All rights reserved.
引用
收藏
页码:292 / 301
页数:10
相关论文
共 43 条
  • [1] Energy extracted from underground rock area by using a horizontal closed loop system in Mutah University/Jordan
    Al-Dabbas, Mohammed Awwad Ali
    Al-Rousan, Ammar A.
    [J]. ENERGY CONVERSION AND MANAGEMENT, 2013, 65 : 744 - 750
  • [2] [Anonymous], 1985, DESIGN DATA MANUAL C
  • [3] Investigation of a solar cooling installation in Tunisia
    Balghouthi, M.
    Chahbani, M. H.
    Guizani, A.
    [J]. APPLIED ENERGY, 2012, 98 : 138 - 148
  • [4] Potential of renewable energy development for water desalination in Tunisia
    BenJemaa, F
    Houcine, I
    Chahbani, MH
    [J]. RENEWABLE ENERGY, 1999, 18 (03) : 331 - 347
  • [5] A performance comparison between a horizontal source and a vertical source heat pump systems for a greenhouse heating in the mild climate Elazig, Turkey
    Benli, Huseyin
    [J]. APPLIED THERMAL ENGINEERING, 2013, 50 (01) : 197 - 206
  • [6] Carli MD, 2010, ENERGY BUILD, V55, P369
  • [7] Geothermal heat pump in heating mode: Modeling and simulation on TRNSYS
    Chargui, R.
    Sammouda, H.
    Farhat, A.
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2012, 35 (07): : 1824 - 1832
  • [8] CFD simulations of horizontal ground heat exchangers: A comparison among different configurations
    Congedo, P. M.
    Colangelo, G.
    Starace, G.
    [J]. APPLIED THERMAL ENGINEERING, 2012, 33-34 : 24 - 32
  • [9] Numerical analysis and experimental validation of heat transfer in ground heat exchangers in alternative operation modes
    Cui, P.
    Yang, H.
    Fang, Z.
    [J]. ENERGY AND BUILDINGS, 2008, 40 (06) : 1060 - 1066
  • [10] A performance comparison between an air-source and a ground-source reversible heat pump
    De Swardt, CA