Simulation and analysis of ±1100kV UHVDC transmission system with hierarchical connection mode based on PSCAD/EMTDC

被引:8
作者
Ren, Ziyuan [1 ]
Li, Jiangtao [1 ]
Yu, Fang [1 ]
He, Jiaxin [1 ]
Liu, Yuhao [1 ]
Sun, Yi [1 ]
机构
[1] Xi An Jiao Tong Univ, Dept Elect Engn, 28 Xianning West Rd, Xian, Shaanxi, Peoples R China
来源
JOURNAL OF ENGINEERING-JOE | 2019年 / 16期
基金
中国国家自然科学基金;
关键词
commutation; earthing; HVDC power transmission; power transmission faults; power system interconnection; invertors; power transmission protection; hierarchical connection mode; ultra-high-voltage direct current transmission system; control logic; voltage balance control module; low-end converter stations; electromagnetic transient equivalent model; simulation software electromagnetic transient design; EMTDC; PSCAD; simulation analysis; DC control system; power systems computer-aided design; PSCAD-EMTDC environment; UHVDC transmission system; Zhundong-Huadong UHVDC transmission project; voltage; 1100; 0; kV;
D O I
10.1049/joe.2018.8837
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
This study first introduces the structure and principle of the control system of ultra-high-voltage direct current (UHVDC) transmission system with hierarchical connection mode, mainly including the whole control logic, the voltage balance control module of high-end and low-end converter stations and the commutation failure prediction function. On this basis, this study sets up an electromagnetic transient equivalent model of UHV AC/DC interconnected system with hierarchical connection mode by simulation software electromagnetic transient design and control/power systems computer-aided design (EMTDC/PSCAD) based on Zhundong-Huadong +/- 1100kV UHVDC transmission project. The simulation analysis was first carried out in steady-state operation. Comparing the electrical parameters of the model under the condition of bipolar total voltage with the actual project, the model is consistent with actual engineering parameters. Next, the simulation was undertaken when single-phase grounding fault occurs on AC bus of rectifier side and inverter side. Finally, simulation waveforms and corresponding conclusion are summarised in this study. The results indicate that the DC control system established with hierarchical connection mode under the PSCAD/EMTDC environment has good adjustment effect and can provide a good reference for practise.
引用
收藏
页码:1687 / 1691
页数:5
相关论文
共 13 条
  • [1] Aidong X, 2008, SO POWER SYSTEM TECH, V2, P14
  • [2] Dongbin L, 2015, INT HIGH VOLT DIR CU, P41
  • [3] Fu Rong, 2017, Electric Power Automation Equipment, V37, P81, DOI 10.16081/j.issn.1006-6047.2017.01.013
  • [4] Hauth R. L, 1982, MULTITERMINAL HVDC C, P14
  • [5] Hui L, 2015, THESIS
  • [6] [李少华 Li Shaohua], 2015, [中国电机工程学报, Proceedings of the Chinese Society of Electrical Engineering], V35, P2409
  • [7] [刘颖 Liu Ying], 2017, [电力系统保护与控制, Power System Protection and Control], V45, P1
  • [8] Liu Zhenya, 2013, Proceedings of the CSEE, V33, P1
  • [9] Miao Lili, 2016, Electric Power Construction, V37, P91, DOI 10.3969/j.issn.1000-7229.2016.02.013
  • [10] CURRENT ORDER COORDINATION IN MULTI-TERMINAL DC SYSTEMS
    NOZARI, F
    GRUND, CE
    HAUTH, RL
    [J]. IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1981, 100 (11): : 4628 - 4635