Patient Warming Excess Heat: The Effects on Orthopedic Operating Room Ventilation Performance

被引:29
作者
Belani, Kumar G. [1 ]
Albrecht, Mark [3 ]
McGovern, Paul D. [4 ]
Reed, Mike [5 ]
Nachtsheim, Christopher [2 ]
机构
[1] Univ Minnesota, Dept Anesthesiol, Minneapolis, MN 55455 USA
[2] Univ Minnesota, Carlson Sch Management, Minneapolis, MN 55455 USA
[3] Natl Marrow Donor Program, Minneapolis, MN 55413 USA
[4] Medway Maritime Hosp, Gillingham, Kent, England
[5] Northumbria Healthcare NHS Fdn Trust, Ashington, Northd, England
关键词
SURGICAL SITE INFECTION; FORCED-AIR; LAMINAR-FLOW; KNEE REPLACEMENT; DEEP INFECTION; JOINT; ANTIBIOTICS; PREVENTION; SYSTEMS; SEPSIS;
D O I
10.1213/ANE.0b013e31825f81e2
中图分类号
R614 [麻醉学];
学科分类号
100217 ;
摘要
BACKGROUND: Patient warming has become a standard of care for the prevention of unintentional hypothermia based on benefits established in general surgery. However, these benefits may not fully translate to contamination-sensitive surgery (i.e., implants), because patient warming devices release excess heat that may disrupt the intended ceiling-to-floor ventilation airflows and expose the surgical site to added contamination. Therefore, we studied the effects of 2 popular patient warming technologies, forced air and conductive fabric, versus control conditions on ventilation performance in an orthopedic operating room with a mannequin draped for total knee replacement. METHODS: Ventilation performance was assessed by releasing neutrally buoyant detergent bubbles (bubbles) into the nonsterile region under the head-side of the anesthesia drape. We then tracked whether the excess heat from upper body patient warming mobilized the bubbles into the surgical site. Formally, a randomized replicated design assessed the effect of device (forced air, conductive fabric, control) and anesthesia drape height (low-drape, high-drape) on the number of bubbles photographed over the surgical site. RESULTS: The direct mass-flow exhaust from forced air warming generated hot air convection currents that mobilized bubbles over the anesthesia drape and into the surgical site, resulting in a significant increase in bubble counts for the factor of patient warming device (P < 0.001). Forced air had an average count of 132.5 versus 0.48 for conductive fabric (P = 0.003) and 0.01 for control conditions (P = 0.008) across both drape heights. Differences in average bubble counts across both drape heights were insignificant between conductive fabric and control conditions (P = 0.87). The factor of drape height had no significant effect (P = 0.94) on bubble counts. CONCLUSIONS: Excess heat from forced air warming resulted in the disruption of ventilation airflows over the surgical site, whereas conductive patient warming devices had no noticeable effect on ventilation airflows. These findings warrant future research into the effects of forced air warming excess heat on clinical outcomes during contamination-sensitive surgery.
引用
收藏
页码:406 / 411
页数:6
相关论文
共 20 条
  • [1] Energy efficiency comparison of forced-air versus resistance heating devices for perioperative hypothermia management
    Bayazit, Yimaz
    Sparrow, Ephraim M.
    [J]. ENERGY, 2010, 35 (03) : 1211 - 1215
  • [2] Forced-air warming: technology, physical background and practical aspects
    Braeuer, Anselm
    Quintel, Michael
    [J]. CURRENT OPINION IN ANESTHESIOLOGY, 2009, 22 (06) : 769 - 774
  • [3] Operating Room Ventilation With Laminar Airflow Shows No Protective Effect on the Surgical Site Infection Rate in Orthopedic and Abdominal Surgery
    Brandt, Christian
    Hott, Uwe
    Sohr, Dorit
    Daschner, Franz
    Gastmeier, Petra
    Rueden, Henning
    [J]. ANNALS OF SURGERY, 2008, 248 (05) : 695 - 700
  • [4] The effect of moving heat sources upon the stratification in rooms ventilated by displacement ventilation
    Brohus, H.
    Balling, K. D.
    Jeppesen, D.
    [J]. INDOOR AIR, 2006, 16 (05) : 356 - 372
  • [5] Effect of forced-air warming on the performance of operating theatre laminar flow ventilation
    Dasari, K. B.
    Albrecht, M.
    Harper, M.
    [J]. ANAESTHESIA, 2012, 67 (03) : 244 - 249
  • [6] Deutsches Institut fur Normung (DIN), 2008, 19464200812 DIN, P1
  • [7] NICE and warm
    Harper, C. M.
    Andrzejowski, J. C.
    Alexander, R.
    [J]. BRITISH JOURNAL OF ANAESTHESIA, 2008, 101 (03) : 293 - 295
  • [8] Does the use of laminar flow and space suits reduce early deep infection after total hip and knee replacement? THE TEN-YEAR RESULTS OF THE NEW ZEALAND JOINT REGISTRY
    Hooper, G. J.
    Rothwell, A. G.
    Frampton, C.
    Wyatt, M. C.
    [J]. JOURNAL OF BONE AND JOINT SURGERY-BRITISH VOLUME, 2011, 93B (01): : 85 - 90
  • [9] Jensen PA., 1998, NIOSH manual of analytical methods, V1, P82, DOI [DOI 10.26616/nioshpub82100, DOI 10.26616/NIOSHPUB82100]
  • [10] Perioperative normothermia to reduce the incidence of surgical-wound infection and shorten hospitalization
    Kurz, A
    Sessler, DI
    Lenhardt, R
    [J]. NEW ENGLAND JOURNAL OF MEDICINE, 1996, 334 (19) : 1209 - 1215