Spatiotemporal variability of ground thermal properties in glacial sediments and implications for horizontal ground heat exchanger design

被引:34
作者
Naylor, Shawn [1 ,2 ]
Ellett, Kevin M. [2 ]
Gustin, Andrew R. [1 ,2 ]
机构
[1] Indiana Univ, Ctr Geospatial Data Anal, Bloomington, IN 47405 USA
[2] Indiana Univ, Indiana Geol Survey, Bloomington, IN 47405 USA
关键词
Soil thermal properties; Geothermal heat pump; Thermal conductivity; Ground temperature; Soil moisture; PUMP; CONDUCTIVITY; PERFORMANCE; SIMULATION; MOISTURE; SANDS;
D O I
10.1016/j.renene.2015.03.006
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
Thorough characterization of the spatiotemporal variability in soil thermal properties can facilitate better designs for horizontal geothermal heat pump (HGHP) systems by reducing ground heat exchanger (GHEX) costs. Results are presented from a new monitoring network installed across a range of glaciated terrains in Indiana (USA), including the first known observations of the dynamic range of thermal conductivity that occurs at the depth of horizontal GHEX installations. In situ thermal conductivity data can vary significantly on a seasonal basis in coarse-grained outwash sediments (0.8-1.4 W m(-1) K-1), whereas clay- and silt-dominated moraine sediments have a dampened seasonal range within 10% of the annual mean. Thermal conductivity across the network ranges from 0.8 to 2.0 W m(-1) K-1 depending on soil parent material, climatic setting, and particularly, soil-moisture variability. Results indicate that the standard industry practice to estimate thermal properties from soil type often leads to suboptimal GHEX design (i.e., GHEX design lengths were 44-52% longer than necessary to meet performance specifications). This research suggests that expanding the characterization of soil thermal properties in specific settings where HGHPs are targeted will improve understanding of the dynamic aspects of ground heat exchange and lead to more optimal HGHP system designs. (C) 2015 Elsevier Ltd. All rights reserved.
引用
收藏
页码:21 / 30
页数:10
相关论文
共 40 条
[1]   Soil thermal conductivity: Effects of density, moisture, salt concentration, and organic matter [J].
Abu-Hamdeh, NH ;
Reeder, RC .
SOIL SCIENCE SOCIETY OF AMERICA JOURNAL, 2000, 64 (04) :1285-1290
[2]  
[Anonymous], 2008, D5334 - 08 Standard Test Method for Determination of Thermal Conductivity of Soil and Soft Rock by Thermal Needle Probe Procedure, P8
[3]  
[Anonymous], 2009, Ground Source Heat Pump Residential and Light Commercial Design and Installation Guide
[4]   Cost optimal analysis of heat pump technology adoption in residential reference buildings [J].
Aste, Niccolo ;
Adhikari, R. S. ;
Manfren, Massimiliano .
RENEWABLE ENERGY, 2013, 60 :615-624
[5]  
Burdick A., 2011, Strategy Guideline: Accurate Heating and Cooling Load Calculations
[6]   The quantitative evaluation of design parameter's effects on a ground source heat pump system [J].
Cho, Honghyun ;
Choi, Jong Min .
RENEWABLE ENERGY, 2014, 65 :2-6
[7]   Simulation of thermal performance of horizontal slinky-loop heat exchangers for ground source heat pumps [J].
Chong, Chiew Shan Anthony ;
Gan, Guohui ;
Verhoef, Anne ;
Garcia, Raquel Gonzalez ;
Vidale, Pier Luigi .
APPLIED ENERGY, 2013, 104 :603-610
[8]  
ClimateMaster, 2013, TRANQUILITY R 20 SIN
[9]  
Decagon Devices, 2012, KD2 PRO THERMAL PROP
[10]   Energy and exergy analysis of a ground-coupled heat pump system with two horizontal ground heat exchangers [J].
Esen, Hikmet ;
Inalli, Mustafa ;
Esen, Mehmet ;
Pihtili, Kazim .
BUILDING AND ENVIRONMENT, 2007, 42 (10) :3606-3615