Experimental and numerical analysis of a cross-flow closed wet cooling tower

被引:47
作者
Jiang, Jing-Jing [1 ]
Liu, Xiao-Hua [1 ]
Jiang, Yi [1 ]
机构
[1] Tsinghua Univ, Dept Bldg Sci, Beijing 100084, Peoples R China
基金
中国国家自然科学基金;
关键词
Closed wet cooling tower; Experiment; Numerical model; Flow pattern; Cross flow; THERMAL PERFORMANCE; COMPUTATIONAL ANALYSIS; MODEL;
D O I
10.1016/j.applthermaleng.2013.08.043
中图分类号
O414.1 [热力学];
学科分类号
摘要
Closed wet cooling tower (CWCT) is an indirect-contact evaporative cooler, in which ambient air, spray water and process water function together. In this study, a cross-flow CWCT unit based on the plate-fin heat exchanger was designed and tested under various conditions in an environmental chamber. The test results suggest that the heat and mass transfer coefficients and the cooling efficiency are remarkably affected by the temperature of the process water and the flow rates of the air, the spray water and the process water. Heat and mass transfer coefficients were correlated based on the sensitive parameters. Two-dimensional steady-state numerical model of the cross-flow CWCT was established and validated by the experimental data. The numerical analyses revealed that the cross-flow CWCT could breakthrough the structure limitation of the commonly parallel/counter-flow configuration and obtain more uniform driving forces, which is beneficial for the cooling performance. The flow pattern optimization of the CWCT shows that air and process water in the opposite direction, spray water and the other fluids in the cross direction is the best flow pattern, which is distinct from the general knowledge of the researches. (C) 2013 Elsevier Ltd. All rights reserved.
引用
收藏
页码:678 / 689
页数:12
相关论文
共 23 条
[1]   Thermal behaviour of closed wet cooling towers for use with chilled ceilings [J].
Facao, J ;
Oliveira, AC .
APPLIED THERMAL ENGINEERING, 2000, 20 (13) :1225-1234
[2]   Numerical simulation of closed wet cooling towers for chilled ceiling systems [J].
Gan, G ;
Riffat, SB .
APPLIED THERMAL ENGINEERING, 1999, 19 (12) :1279-1296
[3]   Theoretical and computational analysis of closed wet cooling towers and its applications in cooling of buildings [J].
Hasan, A ;
Sirén, K .
ENERGY AND BUILDINGS, 2002, 34 (05) :477-486
[4]   Simplification of analytical models and incorporation with CFD for the performance predication of closed-wet cooling towers [J].
Hasan, A ;
Gang, GH .
INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 2002, 26 (13) :1161-1174
[5]   Experimental investigation of two-stage indirect/direct evaporative cooling system in various climatic conditions [J].
Heidarinejad, Ghassem ;
Bozorgmehr, Mojtaba ;
Delfani, Shahram ;
Esmaeelian, Jafar .
BUILDING AND ENVIRONMENT, 2009, 44 (10) :2073-2079
[6]   Experimental investigation into the thermal-flow performance characteristics of an evaporative cooler [J].
Heyns, J. A. ;
Kroeger, D. G. .
APPLIED THERMAL ENGINEERING, 2010, 30 (05) :492-498
[7]  
Kline S.J., 1952, ASME Mechanical Engineering, V75, P3, DOI DOI 10.1016/J.CHAOS.2005.11.046
[8]   The Lewis factor and its influence on the performance prediction of wet-cooling towers [J].
Kloppers, JC ;
Kröger, DG .
INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2005, 44 (09) :879-884
[9]  
Koschenz M., 1995, P 4 INT C INT BUILD
[10]  
KUSUDA T, 1965, HUMIDITY MOISTURE ME