Comparison of Grid Following and Grid Forming Control for a High Inverter Penetration Power System

被引:0
作者
Pattabiraman, Dinesh [1 ]
Lasseter, R. H. [1 ]
Jahns, T. M. [1 ]
机构
[1] Univ Wisconsin, Dept Elect & Comp Engn, 1415 Johnson Dr, Madison, WI 53706 USA
来源
2018 IEEE POWER & ENERGY SOCIETY GENERAL MEETING (PESGM) | 2018年
关键词
Distributed generation; droop control; grid-forming control; grid-following control; frequency-watt; small-signal stability;
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The displacement of synchronous generators with inverter-based sources in the electric grid can results in larger frequency deviations due to lower rotating inertial energy. Existing grid-tied inverters operate as grid-following sources that track the voltage angle of the grid to control their output. Even with inverter fast frequency support, frequency regulation still depends on the remaining synchronous generators. In contrast, grid-forming sources actively control their frequency output, making it possible for them to naturally support the system frequency while sharing a portion of the load change. In this work, the impact of grid-forming and grid-following inverter controllers on the system frequency dynamics is studied and compared. A simple two-source system is modeled, and the small-signal dynamic characteristics are studied at various penetration levels and varying levels of mechanical inertia. The resulting eigenvalue trajectories are presented and these analytical results are validated by the corresponding time-domain plots. The results exhibit significant dynamic response advantages of the grid-forming inverter over its grid-following counterpart, particularly under the most demanding conditions when the penetration level of inverter-based sources reaches high levels and the available system stored inertial energy drops.
引用
收藏
页数:5
相关论文
共 9 条
  • [1] Ackermann T, 2017, IEEE POWER ENERGY M, V15, P61, DOI 10.1109/MPE.2017.2729138
  • [2] [Anonymous], THESIS
  • [3] Voltage-Source Control of PV Inverter in a CERTS Microgrid
    Du, Wei
    Jiang, Qirong
    Erickson, Micah J.
    Lasseter, Robert H.
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2014, 29 (04) : 1726 - 1734
  • [4] Impact of Increased Penetration of Photovoltaic Generation on Power Systems
    Eftekharnejad, Sara
    Vittal, Vijay
    Heydt, Gerald Thomas
    Keel, Brian
    Loehr, Jeffrey
    [J]. IEEE TRANSACTIONS ON POWER SYSTEMS, 2013, 28 (02) : 893 - 901
  • [5] Hart P. J., 2015, 6 INT S POW EL DISTR
  • [6] Hoke A.F., 2017, The frequency-watt function: simulation and testing for the Hawaiian electric companies
  • [7] Kroposki B, 2017, IEEE POWER ENERGY M, V15, P61, DOI 10.1109/MPE.2016.2637122
  • [8] SHARING TRANSIENT LOADS Causes of unequal transient load sharing in islanded microgrid operation
    Paquette, Andrew D.
    Reno, Matthew J.
    Harley, Ronald G.
    Divan, Deepak M.
    [J]. IEEE INDUSTRY APPLICATIONS MAGAZINE, 2014, 20 (02) : 23 - 34
  • [9] Ramasubramanian D, 2016, 2016 POWER SYSTEMS COMPUTATION CONFERENCE (PSCC)