Mechanical Fault Diagnosis of High Voltage Circuit Breakers Based on Variational Mode Decomposition and Multi-Layer Classifier

被引:78
作者
Huang, Nantian [1 ]
Chen, Huaijin [1 ]
Cai, Guowei [1 ]
Fang, Lihua [1 ]
Wang, Yuqiang [2 ]
机构
[1] Northeast Elect Power Univ, Sch Elect Engn, Jilin 132012, Jilin, Peoples R China
[2] State Grid Jibei Elect Power Co Ltd, Maintenance Branch, Beijing 102488, Peoples R China
关键词
mechanical fault diagnosis; high voltage circuit breakers; acceleration sensor; variational mode decomposition; local singular value; one-class support vector machines; VIBRATION ANALYSIS; SUPPORT; ALGORITHM; LMD;
D O I
10.3390/s16111887
中图分类号
O65 [分析化学];
学科分类号
070302 ; 081704 ;
摘要
Mechanical fault diagnosis of high-voltage circuit breakers (HVCBs) based on vibration signal analysis is one of the most significant issues in improving the reliability and reducing the outage cost for power systems. The limitation of training samples and types of machine faults in HVCBs causes the existing mechanical fault diagnostic methods to recognize new types of machine faults easily without training samples as either a normal condition or a wrong fault type. A new mechanical fault diagnosis method for HVCBs based on variational mode decomposition (VMD) and multi-layer classifier (MLC) is proposed to improve the accuracy of fault diagnosis. First, HVCB vibration signals during operation are measured using an acceleration sensor. Second, a VMD algorithm is used to decompose the vibration signals into several intrinsic mode functions (IMFs). The IMF matrix is divided into submatrices to compute the local singular values (LSV). The maximum singular values of each submatrix are selected as the feature vectors for fault diagnosis. Finally, a MLC composed of two one-class support vector machines (OCSVMs) and a support vector machine (SVM) is constructed to identify the fault type. Two layers of independent OCSVM are adopted to distinguish normal or fault conditions with known or unknown fault types, respectively. On this basis, SVM recognizes the specific fault type. Real diagnostic experiments are conducted with a real SF6 HVCB with normal and fault states. Three different faults (i.e., jam fault of the iron core, looseness of the base screw, and poor lubrication of the connecting lever) are simulated in a field experiment on a real HVCB to test the feasibility of the proposed method. Results show that the classification accuracy of the new method is superior to other traditional methods.
引用
收藏
页数:19
相关论文
共 35 条
[1]   Combined VMD-SVM based feature selection method for classification of power quality events [J].
Abdoos, Ali Akbar ;
Mianaei, Peyman Khorshidian ;
Ghadikolaei, Mostafa Rayatpanah .
APPLIED SOFT COMPUTING, 2016, 38 :637-646
[2]   MULTIPLIER METHODS - SURVEY [J].
BERTSEKAS, DP .
AUTOMATICA, 1976, 12 (02) :133-145
[3]  
CIGRE Working Group, 1994, 83 CIGRE
[4]   Variational Mode Decomposition [J].
Dragomiretskiy, Konstantin ;
Zosso, Dominique .
IEEE TRANSACTIONS ON SIGNAL PROCESSING, 2014, 62 (03) :531-544
[5]   Automatic bearing fault diagnosis based on one-class v-SVM [J].
Fernandez-Francos, Diego ;
Martinez-Rego, David ;
Fontenla-Romero, Oscar ;
Alonso-Betanzos, Amparo .
COMPUTERS & INDUSTRIAL ENGINEERING, 2013, 64 (01) :357-365
[6]   Fault detection and diagnosis of diesel engine valve trains [J].
Flett, Justin ;
Bone, Gary M. .
MECHANICAL SYSTEMS AND SIGNAL PROCESSING, 2016, 72-73 :316-327
[7]  
HARRIS FJ, 1978, P IEEE, V66, P51, DOI 10.1109/PROC.1978.10837
[8]   Continuous monitoring of circuit breakers using vibration analysis [J].
Hoidalen, HK ;
Runde, M .
IEEE TRANSACTIONS ON POWER DELIVERY, 2005, 20 (04) :2458-2465
[9]   Support vector machine with genetic algorithm for machinery fault diagnosis of high voltage circuit breaker [J].
Huang, Jian ;
Hu, Xiaoguang ;
Yang, Fan .
MEASUREMENT, 2011, 44 (06) :1018-1027
[10]   An intelligent fault diagnosis method of high voltage circuit breaker based on improved EMD energy entropy and multi-class support vector machine [J].
Huang, Jian ;
Hu, Xiaoguang ;
Geng, Xin .