Post-arc current reconstruction based on actual circuit breaker measurements

被引:1
|
作者
Schavemaker, PH
van der Sluis, L
Pharmatrisanti, A
机构
[1] Delft Univ Technol, Fac Informat Technol & Syst, Power Syst Lab, NL-2628 CD Delft, Netherlands
[2] Jasa Enjiniring, PT PLN Persero, Dept Tekn Listrik, Jakarta 11420, Indonesia
关键词
D O I
10.1049/ip-smt:20020089
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
During short line fault (SLF) tests on three poles of a 72.5 kV, 31.5 kA, 60 Hz SF6 puffer circuit breaker, some remarkably large post-arc currents were measured. For all the measurements performed on the three poles of the specific breaker. no physical post-arc currents could be detected in the measurement data, except for two cases. Both 'post-arc currents' occurred as a last successful interruption of a circuit breaker pole. After these specific interruptions. the circuit breaker poles were degraded so much that only reignitions occurred. In order to verify the observed 'post-arc currents', computations are made based on the more accurate voltage measurements.
引用
收藏
页码:17 / 21
页数:5
相关论文
共 50 条
  • [1] Post-arc current in low voltage vacuum circuit breaker: Measurements and physical peculiarities
    Pavelescu, D
    Nitu, S
    Dumitrescu, G
    Anghelita, P
    ISDEIV: XXTH INTERNATIONAL SYMPOSIUM ON DISCHARGES AND ELECTRICAL INSULATION IN VACUUM, PROCEEDINGS, 2002, 20 : 67 - 70
  • [2] Post-arc current in low-voltage vacuum circuit breaker: Measurements and physical peculiarities
    Pavelescu, D
    Nitu, S
    Dumitrescu, G
    Anghelita, P
    IEEE TRANSACTIONS ON PLASMA SCIENCE, 2003, 31 (05) : 869 - 876
  • [3] Experimental investigations on the post-arc current of the vacuum circuit breaker in an active mechanical DC circuit breaker
    Jia, Shenli
    Tang, Qiang
    Shi, Zongqian
    Mo, Yongpeng
    AIP ADVANCES, 2021, 11 (05)
  • [4] Research on Measurement of Post-Arc Current of Mechanical Vacuum DC Circuit Breaker
    Cheng X.
    Xu P.
    Ge G.
    Li X.
    Tian X.
    Diangong Jishu Xuebao/Transactions of China Electrotechnical Society, 2021, 36 (16): : 3516 - 3524
  • [5] Study on the Proportions of Charged Particles Absorbed by Post-arc Anode in the Post-arc Phase of a Vacuum Circuit Breaker
    Mo, Yongpeng
    Shi, Zongqian
    Jia, Shenli
    Wang, Lijun
    PROCEEDINGS OF THE 27TH INTERNATIONAL SYMPOSIUM ON DISCHARGES AND ELECTRICAL INSULATION IN VACUUM (ISDEIV), VOL 1, 2016, : 337 - 340
  • [6] Study on the effect of arc chamber structures on the post-arc characteristics of generator circuit breaker
    Yin, Jianning
    Zhao, Yongyong
    Duan, Jiandong
    Liang, Shuhua
    ELECTRIC POWER SYSTEMS RESEARCH, 2024, 233
  • [7] Modeling of breakdown during the post-arc phase of a vacuum circuit breaker
    Sarrailh, P.
    Garrigues, L.
    Boeuf, J. P.
    Hagelaar, G. J. M.
    PLASMA SOURCES SCIENCE & TECHNOLOGY, 2010, 19 (06):
  • [8] Two-dimensional simulation of the post-arc phase of a vacuum circuit breaker
    Sarrailh, Pierre
    Garrigues, Laurent
    Hagelaar, Gerjan J. M.
    Boeuf, Jean-Pierre
    Sandolache, Gabriela
    Rowe, Stephan W.
    Jusselin, Benoit
    IEEE TRANSACTIONS ON PLASMA SCIENCE, 2008, 36 (04) : 1046 - 1047
  • [9] Effects of hot SF6 on post-arc circuit breaker design
    Uchii, T
    Nishiwaki, S
    Boggs, S
    IEEE TRANSACTIONS ON POWER DELIVERY, 2004, 19 (01) : 124 - 130
  • [10] Simulation of post-arc dielectric recovery characteristics of DC vacuum circuit breaker
    Liu, Xiaoming
    Yu, Deen
    Zou, Jiyan
    Zhenkong Kexue yu Jishu Xuebao/Journal of Vacuum Science and Technology, 2014, 34 (12): : 1285 - 1289