Monitoring of interarea oscillation mode by synchronized phasor measurement

被引:84
作者
Kakimoto, N [1 ]
Sugumi, M
Makino, T
Tomiyama, K
机构
[1] Kyoto Univ, Kyoto 6168510, Japan
[2] Kansai Elect Power Co, Osaka 5300005, Japan
关键词
global positioning system (GPS); interarea oscillation mode; monitoring; power system stability; synchronized phasor measurement;
D O I
10.1109/TPWRS.2005.861960
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
There is a low-frequency interarea oscillation mode in middle and western 60-Hz areas of Japan. Its stability determines available transfer capacity of a tie-line. We propose a method of monitoring its stability by phasor measurements synchronized using the global positioning system. The phase angle between two places deviates randomly. However, its Fourier spectrum shows a clear peak corresponding to the interarea mode. We estimate its frequency and damping from the spectrum. The estimation results agree well with those obtained by curve fitting for large disturbances. It is also possible to estimate the eigenvector. We examine how the eigenvalue varies with the total generation and power flow in the areas.
引用
收藏
页码:260 / 268
页数:9
相关论文
共 18 条
[1]   SYNCHRONIZED PHASOR MEASUREMENTS OF A POWER-SYSTEM EVENT [J].
BURNETT, RO ;
MICHEL, G ;
BUTTS, MM ;
MURPHY, RJ ;
CEASE, TW ;
CENTENO, V ;
PHADKE, AG .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1994, 9 (03) :1643-1649
[2]  
Centeno V., 1993, IEEE Computer Applications in Power, V6, P12, DOI 10.1109/67.238199
[3]   AN ALGORITHM FOR MACHINE CALCULATION OF COMPLEX FOURIER SERIES [J].
COOLEY, JW ;
TUKEY, JW .
MATHEMATICS OF COMPUTATION, 1965, 19 (90) :297-&
[4]   MEASUREMENT OF VOLTAGE PHASE FOR THE FRENCH FUTURE DEFENSE PLAN AGAINST LOSSES OF SYNCHRONISM [J].
DENYS, P ;
COUNAN, C ;
HOSSENLOPP, L ;
HOLWECK, C .
IEEE TRANSACTIONS ON POWER DELIVERY, 1992, 7 (01) :62-69
[5]   Coordinated defense plan protects against transient instabilities [J].
Faucon, O ;
Dousset, L .
IEEE COMPUTER APPLICATIONS IN POWER, 1997, 10 (03) :22-26
[6]  
HASHIGUCHI T, 2003, IEEJ T POWER ENERGY, V12, P1471
[7]   Keeping an eye on power system dynamics [J].
Hauer, J ;
Trudnowski, D ;
Rogers, G ;
Mittelstadt, B ;
Litzenberger, W ;
Johnson, J .
IEEE COMPUTER APPLICATIONS IN POWER, 1997, 10 (04) :50-54
[8]   INITIAL RESULTS IN PRONY ANALYSIS OF POWER-SYSTEM RESPONSE SIGNALS [J].
HAUER, JF ;
DEMEURE, CJ ;
SCHARF, LL .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1990, 5 (01) :80-89
[9]   RANDOM NUMBER GENERATORS [J].
HULL, TE ;
DOBELL, AR .
SIAM REVIEW, 1962, 4 (03) :230-+
[10]   Instability of interarea oscillation mode by autoparametric resonance [J].
Kakimoto, N ;
Nakanishi, A ;
Tomiyama, K .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2004, 19 (04) :1961-1970