Analysis of air source heat-pump system assisted by solar energy

被引:1
作者
Su, Shunyu [1 ]
Huang, Qin [1 ]
Chen, Jian [1 ]
机构
[1] Wuhan Univ Sci & Technol, Coll Urban Construct, Wuhan 430070, Peoples R China
来源
ELECTRICAL POWER & ENERGY SYSTEMS, PTS 1 AND 2 | 2012年 / 516-517卷
关键词
Heat-pump; Solar energy; Mass flux; Exhaust bypass; DEFROSTING METHOD; EXCHANGERS;
D O I
10.4028/www.scientific.net/AMR.516-517.257
中图分类号
O414.1 [热力学];
学科分类号
摘要
The steady state distributed parameter model of heat exchangers in a heat-pump system was established in this paper. The calculating results of refrigerant quantities in the heat-exchangers show that refrigerant charge quantity in heating operating condition is less than that in refrigeration operating condition. Based on the differences of refrigerant mass flux between refrigeration and heating conditions, the exhaust bypass method to improve the operation efficiency of the heat-pump system was presented. And in order to prevent frosting on the surface of outdoor heat exchanger of the air source heat-pump, the solar energy assisted strategy was also applied in the heat-pump system.
引用
收藏
页码:257 / 260
页数:4
相关论文
共 11 条
[1]   Frost retardation of an air-source heat pump by the hot gas bypass method [J].
Byun, Ju-Suk ;
Lee, Jinho ;
Jeon, Chang-Duk .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2008, 31 (02) :328-334
[2]  
Chen Z. J., 1998, REFRIGERATION SYSTEM
[3]   Advances in heat pump systems: A review [J].
Chua, K. J. ;
Chou, S. K. ;
Yang, W. M. .
APPLIED ENERGY, 2010, 87 (12) :3611-3624
[4]   Hot gas defrost model development and validation [J].
Hoffenbecker, N ;
Klein, SA ;
Reindl, DT .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2005, 28 (04) :605-615
[5]   Air-side heat transfer characteristics of flat plate finned-tube heat exchangers with large fin pitches under frosting conditions [J].
Lee, Mooyeon ;
Kim, Yonghan ;
Lee, Hosung ;
Kim, Yongchan .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2010, 53 (13-14) :2655-2661
[6]   Control strategy and experimental study on a novel defrosting method for air-source heat pump [J].
Liang, Cai-Hua ;
Zhang, Xiao-Song ;
Li, Xiu-Wei ;
Chen, Zhen-Qian .
APPLIED THERMAL ENGINEERING, 2010, 30 (8-9) :892-899
[7]  
[罗刚 Luo Gang], 2005, [流体机械, Fluid Machinery], V33, P39
[8]   Improved indoor thermal comfort during defrost with a novel reverse-cycle defrosting method for air source heat pumps [J].
Qu Minglu ;
Xia Liang ;
Deng, Shiming ;
Jiang Yiqiang .
BUILDING AND ENVIRONMENT, 2010, 45 (11) :2354-2361
[9]  
Su S. Y., 2009, J HVAC, V39, P128
[10]   Numerical simulation of operating performance of heat exchangers in a residential split air-conditioner [J].
Su, Shunyu ;
Tian, Tian ;
Chen, Jian .
ADVANCED BUILDING MATERIALS, PTS 1-4, 2011, 250-253 (1-4) :3913-3918