Fault Location in Distribution Systems Considering the non-liner Profile Characteristic of Voltage Sag on the Bus

被引:0
|
作者
Zheng, Tianwen [1 ]
Yang, Jianwen [1 ]
Xiao, Xianyong [1 ]
Wang, Ying [1 ]
机构
[1] Sichuan Univ, Coll Elect Engn & Informat Technol, Chengdu 610064, Peoples R China
来源
PROGRESS IN POWER AND ELECTRICAL ENGINEERING, PTS 1 AND 2 | 2012年 / 354-355卷
关键词
fault location; distribution system; voltage sag; non-liner profile; analytical expression;
D O I
10.4028/www.scientific.net/AMR.354-355.1088
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The bus will experience different voltage sag when fault occurs at different location. Based on the non-liner profile characteristic of voltage sag measured at the bus, the paper proposes a new fault location method. Firstly, it obtains the analytical expression of each section based on the relationship between voltage sag and fault location. Then calculate the fault distance using chord secant method and identify the faulted section through the minimal deviation of fault distance. The combined two results of fault distance and faulted section make fault location accurately. It overcomes the difficulty of radial power distribution systems fault location. Through simulating for the IEEE 13 node test feeder with different faults, including various fault resistance, loading variation and the connected distributed generation, it proves the method's accuracy and effectiveness.
引用
收藏
页码:1088 / 1092
页数:5
相关论文
共 37 条
  • [21] Automated fault location scheme for low voltage smart distribution systems
    Naderi, Salar
    Ketabi, Abbas
    Sadeghkhani, Iman
    ELECTRONICS LETTERS, 2023, 59 (24)
  • [22] A voltage-based fault location algorithm for medium voltage active distribution systems
    Arsoniadis, Charalampos G.
    Apostolopoulos, Christos A.
    Georgilakis, Pavlos S.
    Nikolaidis, Vassilis C.
    ELECTRIC POWER SYSTEMS RESEARCH, 2021, 196
  • [23] A novel high impedance fault location for distribution systems considering distributed generation
    Bretas, Arturo S.
    Moreto, Miguel
    Salim, Rodrigo H.
    Pires, Luciano O.
    2006 IEEE/PES TRANSMISSION & DISTRIBUTION CONFERENCE & EXPOSITION: LATIN AMERICA, VOLS 1-3, 2006, : 433 - +
  • [24] Fault location considering load uncertainty and distributed generation in power distribution systems
    Mora-Florez, Juan J.
    Herrera-Orozco, Ricardo A.
    Bedoya-Cadena, Andres F.
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2015, 9 (03) : 287 - 295
  • [25] Low Voltage Zones to Support Fault Location in Distribution Systems With Smart Meters
    Trindade, Fernanda C. L.
    Freitas, Walmir
    IEEE TRANSACTIONS ON SMART GRID, 2017, 8 (06) : 2765 - 2774
  • [26] Time domain analysis for fault location in power distribution systems considering the load dynamics
    Cifuentes-Chaves, H.
    Mora-Florez, J.
    Perez-Londono, S.
    ELECTRIC POWER SYSTEMS RESEARCH, 2017, 146 : 331 - 340
  • [27] Fault Location in Neutral Non-effectively Grounded Distribution Systems Using Phase Current and Line-to-line Voltage
    Tang, Jinrui
    Yin, Xianggen
    Wen, Minghao
    Zhang, Zhe
    ELECTRIC POWER COMPONENTS AND SYSTEMS, 2014, 42 (13) : 1371 - 1385
  • [28] Ground Fault Location Using the Low-Voltage-Side Recorded Data in Distribution Systems
    Jia, Ke
    Ren, Zhefeng
    Bi, Tianshu
    Yang, Qixun
    IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2015, 51 (06) : 4994 - 5001
  • [29] Distribution systems high impedance fault location: A spectral domain model considering parametric error processing
    Nunes, J. U. N.
    Bretas, A. S.
    Bretas, N. G.
    Herrera-Orozco, A. R.
    Iurinic, L. U.
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2019, 109 : 227 - 241
  • [30] A Travelling Wave Detector Based Fault Location Device and Data Recorder for Medium Voltage Distribution Systems
    Jahromi, Ali Tashakkori
    Wolfs, Peter
    Islam, Syed
    PROCEEDINGS OF THE 2016 AUSTRALASIAN UNIVERSITIES POWER ENGINEERING CONFERENCE (AUPEC), 2016,