Model of distribution transformers winding for lightning

被引:0
作者
de Salles, Credson [1 ]
Barreira Martinez, Manuel Luis [1 ]
机构
[1] Univ Fed Itajuba, Elect Syst & Energy Inst, BR-37500050 Minas Gerasis, Brazil
来源
2007 IEEE LAUSANNE POWERTECH, VOLS 1-5 | 2007年
关键词
circuit modeling; testing; transformers; transient analysis;
D O I
10.1109/PCT.2007.4538633
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
This paper presents a mathematical model for distribution transformers winding to simulate its lightning impulse behavior. The aim is to investigate the real source of some signals present in the current wave of lightning impulse test. These signals are generally attached to the testing system and not to the testing transformer. This hind of interpretation can consider approved a failed transformer. The procedure takes into account the comparison between lightning impulse tests on actual transformers and their simulation results. The main contribution of this paper regarding previous publications [1]-[2] is concerning the current wave of chopped impulses. The idea is to use the chopped waves to confirm the existence of small failures on tested transformers that present some of noises in the current wave of fall impulses.