Experimental investigation of the effect of different nanofluids on the thermal performance of a wet cooling tower using a new method for equalization of ambient conditions

被引:33
作者
Imani-Mofrad, Peyman [1 ]
Heris, Saeed Zeinali [1 ,2 ]
Shanbedi, Mehdi [1 ]
机构
[1] Ferdowsi Univ Mashhad, Dept Chem Engn, Fac Engn, Mashhad, Iran
[2] Univ Tabriz, Fac Chem & Petr Engn, Tabriz, Iran
关键词
Nanofluid; Cooling tower; Graphene; Metal oxide nanoparticles; Heat transfer enhancement; DRIFT ELIMINATORS; HEAT-TRANSFER; OPTIMIZATION; CROSSWIND; TEMPERATURE; EVAPORATION; ENERGY;
D O I
10.1016/j.enconman.2017.12.056
中图分类号
O414.1 [热力学];
学科分类号
摘要
In this study, first a new method has been presented for equalization of ambient conditions in different experiments on cooling towers. Next, using this method, the effect of four nanofluids including Zinc Oxide/Water, Silica/Water, Alumina/Water, and Graphene/Water has been investigated experimentally on the thermal performance of a wet cooling tower with a cross flow. The nanofluids have been studied at concentrations of 0.02, 0.05, and 0.08 wt% and the parameters of cooling range, effectiveness of the cooling tower, evaporation rate, the cooling tower characteristic, and volumetric heat transfer coefficient have been calculated and compared with each other. The different behavior of these nanofluids on the thermal performance of the cooling tower has also been indicated. For example, with the use of Graphene/Water at 0.02 wt%, the effectiveness and cooling tower characteristic have increased by 8.3% and 36%, respectively in comparison with pure water. On the other hand, with the use of Alumina/Water nanofluid across all the concentrations, the thermal performance of the cooling tower has weakened in comparison with pure water, and for example at 0.08 wt% of this nanofluid, the cooling tower characteristic has diminished by 14.7% in relation with pure water. Furthermore, by comparing the investigated nanofluids, it was found that Graphene/Water has resulted the best thermal performance in the cooling tower across all the concentrations, when compared with other investigated nanofluids. Moreover, the best thermal performance of the cooling tower by Graphene/Water has been obtained at 0.02 wt%, at which the volumetric heat transfer coefficient has increased by 36.2%, in comparison with pure water.
引用
收藏
页码:23 / 35
页数:13
相关论文
共 30 条
  • [1] Experimental investigation on thermal performance of natural draft wet cooling towers employing an innovative wind-creator setup
    Alavi, Seyed Rashid
    Rahmati, Mehdi
    [J]. ENERGY CONVERSION AND MANAGEMENT, 2016, 122 : 504 - 514
  • [2] [Anonymous], 1995, EASTMAN ENHANCING TH
  • [3] A novel approach for energy and water conservation in wet cooling towers by using MWNTs and nanoporous graphene nanofluids
    Askari, S.
    Lotfi, R.
    Seifkordi, A.
    Rashidi, A. M.
    Koolivand, H.
    [J]. ENERGY CONVERSION AND MANAGEMENT, 2016, 109 : 10 - 18
  • [4] BUCK AL, 1981, J APPL METEOROL, V20, P1527, DOI 10.1175/1520-0450(1981)020<1527:NEFCVP>2.0.CO
  • [5] 2
  • [6] Effects of nanoparticles on nanofluid droplet evaporation
    Chen, Ruey-Hung
    Phuoc, Tran X.
    Martello, Donald
    [J]. INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2010, 53 (19-20) : 3677 - 3682
  • [7] Cheremisinoff NP, 2006, COOLING TOWERS SELEC
  • [8] A review on preparation, characterization, properties and applications of nanofluids
    Devendiran, Dhinesh Kumar
    Amirtham, Valan Arasu
    [J]. RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2016, 60 : 21 - 40
  • [9] The investigation of cooling tower packing in various arrangements
    Goshayshi, HR
    Missenden, JF
    [J]. APPLIED THERMAL ENGINEERING, 2000, 20 (01) : 69 - 80
  • [10] A numerical study on the mechanism and optimization of wind-break structures for indirect air-cooling towers
    Gu, Hongfang
    Wang, Haijun
    Gu, Yuqian
    Yao, Jianan