Using plate thermometer measurements to calculate incident heat radiation

被引:22
作者
Haggkvist, Andreas [1 ]
Sjostrom, Johan [1 ]
Wickstrom, Ulf [1 ,2 ]
机构
[1] SP Tech Res Inst Sweden, S-50115 Boras, Sweden
[2] Lulea Tech Univ, Dept Civil Environm & Nat Resources Engn, Lulea, Sweden
关键词
Fire; plate thermometer; incident heat radiation; irradiance; heat flux meters; measuring instrument; thermal exposure; FIRE;
D O I
10.1177/0734904112459264
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
The plate thermometer is a device used mainly to measure temperatures in fire resistance tests according to ISO 834-1 and EN 1363-1 and to measure the so-called adiabatic surface temperature. However, it can also be used to measure incident radiant heat flux () as a simpler, more robust and less-expensive alternative to water-cooled heat flux meters. The accuracy of the measured is subject to simplifications in the heat transfer analysis model and uncertainties of parameters such as convective heat transfer coefficients, emissivities and ambient gas temperatures. This study investigates the accuracy of the model itself, isolated from the uncertainties of the physical surrounding, by comparing a simple one-dimensional model to the results of finite element modelling. The so-obtained model includes a heat transfer coefficient due to heat losses of the plate thermometer, found to be K-PT = 8 W/m(2) K and a heat storage lumped heat capacity C-PT = 4200 J/m(2) K for an ISO/EN standard plate thermometer. The model is also compared to real field experiments.
引用
收藏
页码:166 / 177
页数:12
相关论文
共 13 条
[1]  
[Anonymous], 2200722008 ISO
[2]  
Arvidsson M, 2005, 200533 SP TECHN RES
[3]   Recent advances in fire-structure analysis [J].
Duthinh, Dat ;
McGrattan, Kevin ;
Khaskia, Abed .
FIRE SAFETY JOURNAL, 2008, 43 (02) :161-167
[4]   TRANSIENT PLANE SOURCE TECHNIQUES FOR THERMAL-CONDUCTIVITY AND THERMAL-DIFFUSIVITY MEASUREMENTS OF SOLID MATERIALS [J].
GUSTAFSSON, SE .
REVIEW OF SCIENTIFIC INSTRUMENTS, 1991, 62 (03) :797-804
[5]  
Haggkvist A, 2009, 2009183 NR LUL U TEC, V2009, P183
[6]   Measuring incident radiant heat flux using the plate thermometer [J].
Ingason, Haukur ;
Wickstrom, Ulf .
FIRE SAFETY JOURNAL, 2007, 42 (02) :161-166
[7]  
Lonnermark A, 2010, 201018 SP TECHN RES, V2010, P18
[8]  
Lonnermark A, 2005, 200521 SP TECHN RES
[9]  
Special Metals Corporation, SPEC MET CORP TECHN
[10]  
STERNER E, 1990, 199005 SP TECHN RES