Load flow and contingency analysis for transmission line outage

被引:14
作者
Aeggegn, Dessalegn Bitew [1 ]
Salau, Ayodeji Olalekan [2 ]
Gebru, Yalew [1 ]
机构
[1] Debre Markos Inst Technol, Dept Elect & Comp Engn, Debre Marqos, Ethiopia
[2] Afe Babalola Univ, Dept Elect Elect & Comp Engn, Ado Ekiti, Nigeria
关键词
contingency analysis; DIgSILENT software; line outage; Newton Raphson method;
D O I
10.24425/aee.2020.133919
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In recent years, power systems have been pushed to operate above their limits due to the increase in the demand for energy supply and its usage. This increase is accompanied by various kinds of obstructions in power transmission systems. A power system is said to be secured when it is free from danger or risk. Power systems security deals with the ability of the system to withstand any contingencies without any consequences. Contingencies are potentially harmful disturbances which occur during the steady state operation of a power system. Load flow constitutes the most important study in a power system for planning, operation, and expansion. Contingency selection is performed by calculating two kinds of performance indices; an active performance index (PIP) and reactive power performance index (PIV) for a single transmission line outage. In this paper, with the help of the Newton Raphson method, the PIP and PIV were calculated with DIgSILENT Power Factory simulation software and contingency ranking was performed. Based on the load flow results and performance indexes, the Ethiopian Electric Power (EEP) North-West region network is recommended for an upgrade or the reactive power or series compensators should be constructed on the riskiest lines and substations.
引用
收藏
页码:581 / 594
页数:14
相关论文
共 14 条
[1]  
Agajie TF, 2019, IEEE INT CONF SIG PR, P292, DOI [10.1109/ispcc48220.2019.8988401, 10.1109/ISPCC48220.2019.8988401]
[2]   Contingency selection and ranking for composite power system reliability evaluation [J].
Al-Shaalan A.M. .
Journal of King Saud University - Engineering Sciences, 2020, 32 (02) :141-147
[3]  
Burada S., 2016, 2016 IEEE 1st International Conference on Power Electronics, Intelligent Control and Energy Systems (ICPEICES), P1, DOI DOI 10.1109/ICPEICES.2016.7853352
[4]  
Chaitanya C.K., 2013, INT J INNOVATIVE RES, V2, P109
[5]  
Kirschen D., 2004, ELECT J, V17, P29, DOI DOI 10.1016/J.TEJ.2003.12.005
[6]  
Koval D.O., 2009, IEEE IND COMM POW SY, DOI [10.1109/icps.2009.5463941., DOI 10.1109/ICPS.2009.5463941]
[7]  
Mohamed Salah Eldeen Gasim, 2012, ZAYT U INT ENG C DES, pI3
[8]  
Raj N, 2016, C IND ELECT APPL, P7, DOI 10.1109/IEACON.2016.8067347
[9]  
Ravindra S., 2015, IJIREEICE, V3, P46, DOI [10.17148/IJIREEICE.2015.3109, DOI 10.17148/IJIREEICE.2015.3109]
[10]  
Robak S, 2017, INT SCI CONF ELECTR, P18