Modeling and enhanced control of DFIG under unbalanced grid voltage conditions

被引:75
作者
Hu, Jiabing [1 ]
He, Yikang [1 ]
机构
[1] Zhejiang Univ, Coll Elect Engn, Hangzhou 310027, Peoples R China
基金
中国国家自然科学基金;
关键词
Voltage unbalance; Wind turbines; Doubly fed induction generator (DFIG); Instantaneous active and reactive powers; Proportional integral plus resonant (PI plus R) controller; FED INDUCTION GENERATOR; WIND TURBINES;
D O I
10.1016/j.epsr.2008.06.017
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents a mathematical model of a doubly fed induction generator (DFIG) based on stator voltage orientation (SVO) in the positive and negative synchronous reference frames under unbalanced grid voltage conditions. The oscillations of the DFIG electromagnetic torque and the stator active and reactive powers are fully described during grid voltage unbalance. A new rotor current controller implemented in the positive synchronous reference frame is proposed. The controller consists of a proportional integral (PI) regulator and a harmonic resonant (R) compensator tuned at twice the grid frequency. Thus, the positive and negative sequence components of DFIG rotor currents are directly regulated by the PI + R controller without the need of involving positive and negative sequence decomposition, which indeed improves the dynamic performance of DFIG-based wind power generation system during small steady-state and relatively larger transient network unbalances. The theoretical analysis and the feasibility of the proposed unbalanced control scheme are validated by simulation studies on a 1.5-MW wind-turbine driven DFIG system. Compared with conventional single PI current control design, the proposed control scheme results in significant elimination of either DFIG power or torque oscillation under unbalanced grid voltage conditions. (C) 2008 Elsevier B.V. All rights reserved.
引用
收藏
页码:273 / 281
页数:9
相关论文
共 14 条
  • [1] [Anonymous], P EUR C POW EL APPL
  • [2] [Anonymous], IEEE T ENER IN PRESS
  • [3] Brekken T, 2003, IEEE POWER ELECTRON, P760
  • [4] Chomát M, 2002, IEE CONF PUBL, P329, DOI 10.1049/cp:20020138
  • [5] Hu J.B., 2006, Journal of Zhejiang University Science A, V7, P1757, DOI DOI 10.1631/JZUS.2006.A1757
  • [6] Ridethrough of wind turbines with doubly-fed induction generator during a voltage dip
    Morren, J
    de Haan, SWH
    [J]. IEEE TRANSACTIONS ON ENERGY CONVERSION, 2005, 20 (02) : 435 - 441
  • [7] NASS TI, 2002, IEEE WORKSH WIND POW, P17
  • [8] *NAT GRID TRANSC, 2004, APP 1 EXTR GRID COD
  • [9] Doubly fed induction generator using back-to-back PWM converters and its application to variable-speed wind-energy generation
    Pena, R
    Clare, JC
    Asher, GM
    [J]. IEE PROCEEDINGS-ELECTRIC POWER APPLICATIONS, 1996, 143 (03): : 231 - 241
  • [10] PETERSON A, 2006, 35 ANN IEEE POW EL S, V1, P482