A fundamental study on electrical insulation of N2/SF6 gas-insulated electric power apparatus

被引:1
|
作者
Sato, H [1 ]
Morita, K [1 ]
Kikkawa, T [1 ]
Hayakawa, N [1 ]
Okubo, H [1 ]
机构
[1] Nagoya Univ, Grad Sch, Engn Res Dept, Nagoya, Aichi, Japan
关键词
N2/SF6 gas mixture; GIS; insulation design; impulse ratio; tank diameter;
D O I
10.1002/eej.1163
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In this paper, we carried out a case study on fundamental insulation design for the application of N-2/SF6 gas mixtures to a 275-kV gas-insulated busbar. First, we investigated the impulse ratio in N-2/SF6 gas mixtures and point out that the insulation design might be based on the negative switching impulse voltage in the case of lower SF6 content. Second, we estimated the tank diameter and SF6 gas amount with consideration of the electric field strength on conductor surface and temperature rise in gas mixtures. We clarified that the tank diameter at the lower SF6 content is mainly determined by the electric field strength on the conductor surface and quantified the optimum gas pressure and SF6 content for a target reduction of SF6 gas amount. (C) 2002 Wiley Periodicals, Inc.
引用
收藏
页码:9 / 16
页数:8
相关论文
共 50 条
  • [31] 550 KV SF6 GAS-INSULATED SWITCHGEAR FOR THE ITAIPU HYDRO-POWER STATION
    SZENTEVARGA, HP
    BROWN BOVERI REVIEW, 1981, 68 (3-4): : 157 - 159
  • [32] Separation and concentration of SF6 from N2/SF6 gas mixtures
    Nam, S. E.
    Park, A.
    Kim, B. S.
    Park, Y. I.
    EUROMEMBRANE CONFERENCE 2012, 2012, 44 : 970 - 971
  • [33] Effect of Epoxy Coating on Particle Movement In SF6/N2 Gas Insulated Busduct
    Rao, M. Raghavendra
    Amarnath, J.
    2011 ANNUAL REPORT CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA, VOLS 1 AND 2, 2011, : 211 - 214
  • [34] Technology of leakage-gas blocking with pressure in SF6 insulated power apparatus
    Shanghai Electric Power Corporation, Shanghai 200030, China
    不详
    Gaoya Dianqi, 2007, 5 (378-379+383):
  • [35] Compact Design of 330 kV SF6/N2 Mixed Gas Insulated Busbar
    Pang W.
    Wu X.
    Wu S.
    Yang Z.
    Yang X.
    Hou H.
    Gaodianya Jishu/High Voltage Engineering, 2020, 46 (03): : 1043 - 1050
  • [36] Effects due to Metallic Particle Contaminations in SF6/N2 Gas Insulated Busduct
    Nagabhushan, P.
    Amarnath, J.
    Subbarayudu, D.
    2011 ANNUAL REPORT CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA, VOLS 1 AND 2, 2011, : 522 - 525
  • [37] Experimental Study of Synergism in N2 and SF6 Gas Mixtures
    Hiziroglu, Huseyin R.
    Bian, Xingming
    Lu, Tiebing
    PROCEEDINGS OF THE 2020 3RD IEEE INTERNATIONAL CONFERENCE ON DIELECTRICS (ICD 2020), 2020, : 814 - 817
  • [38] Research progress on photoacoustic SF6 decomposition gas sensor in gas-insulated switchgear
    Yin, Xukun
    Su, Yongliang
    Xi, Teli
    Chen, Baisong
    Zhang, Le
    Zhang, Xueshi
    Liu, Lixian
    Shao, Xiaopeng
    JOURNAL OF APPLIED PHYSICS, 2022, 131 (13)
  • [39] Temperature Effect on the Insulation Performance of SF6/N2 Gas Mixture at a Constant Volume
    Zheng, Yu
    Zhou, Wenjun
    Yang, Shuai
    Qiao, Shengya
    Huang, Jiarui
    Qin, Zhaoyu
    2016 IEEE INTERNATIONAL CONFERENCE ON HIGH VOLTAGE ENGINEERING AND APPLICATION (ICHVE), 2016,
  • [40] Fundamental insulation characteristics of air, N2, CO2, N2/O2, and SF6/N2 mixed gases
    Rokunohe, T
    Yagihashi, Y
    Endo, F
    Oomori, T
    ELECTRICAL ENGINEERING IN JAPAN, 2006, 155 (03) : 9 - 17