Single-ended multi-method phasor-based approach for optimized fault location on transmission lines

被引:18
作者
Lopes, Felipe, V [1 ]
Leite Jr, Eduardo Jorge S.
Ribeiro, Joao Paulo G.
Piardi, Artur B.
Scheid, Allan, V [2 ]
Zat, Guilherme [2 ]
Espinoza, Renzo G. F.
机构
[1] Fed Univ Paraiba UFPB, Joao Pessoa, Paraiba, Brazil
[2] Itaipu Technol Pk Fdn, Foz Do Iguacu, Brazil
关键词
Phasor-based methods; Multi-method solution; Single-ended fault location; Transmission line;
D O I
10.1016/j.epsr.2022.108361
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents the development of a transmission line multi-method single-ended phasor-based fault location (SEPHFL) approach in a real digital fault recorder (DFR). Unlike classical solutions, it processes the outputs taken from different SEPHFL methods, allowing the calculation of accurate punctual fault distances, such as traditional approaches do, and reliable fault search fields, which is innovative from the point of view of SEPHFL applications. To properly select the algorithms to be used in the proposed solution, a Real-Time Digital Simulator (RTDS) is used to carry out massive hardware-in-the-loop fault simulations on 500 kV and 230 kV test power systems. Firstly, the DFR hardware capabilities are analyzed to identify SEPHFL methods with compatible requirements, and then, eight SEPHFL methods are chosen to be embedded in the DFR. Parametric studies in a fully controllable 500 kV test power network are carried out, varying the system operation conditions and fault features. Based on the obtained results, three techniques are selected to compose the proposed multi-method SEPHFL solution, which is finally implemented in the DFR and validated through tests in a realistic IEEE benchmark 230 kV/60 Hz system. The obtained results show the proposed approach is able to calculate accurate punctual fault distance estimations, with the advantage of providing a reliable search field, which can be used to optimize line inspection procedures, mainly when there is uncertainty on the punctual fault location estimations provided by traditional technologies.
引用
收藏
页数:10
相关论文
共 16 条
  • [11] Phasor-based fault location challenges and solutions for transmission lines equipped with high-speed time-domain protective relays
    Lopes, Felipe, V
    Leite Jr, Eduardo Jorge S.
    Ribeiro, Joao Paulo G.
    Piardi, Artur B.
    Fabian Espinoza, Renzo G.
    Scheid, Allan, V
    Zat, Guilherme
    Otto, Rodrigo B.
    [J]. ELECTRIC POWER SYSTEMS RESEARCH, 2020, 189 (189)
  • [12] Saha MM, 2010, POWER SYST, P1, DOI 10.1007/978-1-84882-886-5
  • [13] DEVELOPMENT OF A NEW TYPE FAULT LOCATOR USING THE ONE-TERMINAL VOLTAGE AND CURRENT DATA
    TAKAGI, T
    YAMAKOSHI, Y
    YAMAURA, M
    KONDOW, R
    MATSUSHIMA, T
    [J]. IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1982, 101 (08): : 2892 - 2898
  • [14] ACCURATE FAULT IMPEDANCE LOCATING ALGORITHM
    WISZNIEWSKI, A
    [J]. IEE PROCEEDINGS-C GENERATION TRANSMISSION AND DISTRIBUTION, 1983, 130 (06) : 311 - 314
  • [15] A distance protection relay for a 1000-kV UHV transmission line
    Xu, Z. Y.
    Huang, S. F.
    Ran, Li
    Liu, J. F.
    Qin, Y. L.
    Yang, Q. X.
    He, J. L.
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2008, 23 (04) : 1795 - 1804
  • [16] Zimath SL, 2010, 2010 IEEE PES TRANSMISSION AND DISTRIBUTION CONFERENCE AND EXPOSITION: SMART SOLUTIONS FOR A CHANGING WORLD