Power quality assessment of large motor starting and loading for the integrated steel-making cogeneration facility

被引:0
|
作者
Hsu, CT [1 ]
Chuang, HJ [1 ]
机构
[1] So Taiwan Univ Technol, Dept Elect Engn, Tainan, Taiwan
关键词
power quality; cogeneration; motor starting;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents the power quality assessment of large synchronous motor starting and loading in the integrated steel-making cogeneration facility. To execute the transient stability analysis, the proper mathematical models and the accurate parameters of the cogeneration units, excitation systems, governor systems, load and static var compensators (SVC) are investigated in detail. Four study cases with or without considering the connection of the power grid, the installation of autotransformer starter and SVC are performed to demonstrate the dynamic responses of system frequency, voltage and cogeneration units due to motor starting and loading. Also, the voltage sag ride-through curve of sensitivity load has been included and a power quality index (PQI) due to voltage variation in the assessment period has been proposed to find the impact of motor starting and loading on the power quality of the cogeneration system. It is concluded that the system dynamic responses and PQI values have better performances if the autotransformer starter is applied with either the regulation of SVC system or connecting to the bulk power grid.
引用
收藏
页码:59 / 66
页数:8
相关论文
共 7 条
  • [1] Power quality assessment of large motor starting and loading for the integrated steel-making cogeneration facility
    Hsu, Cheng-Ting
    Chuang, Hui-Jen
    Chen, Chao-Shun
    IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2007, 43 (02) : 395 - 402
  • [2] Transient stability study of the large synchronous motors starting and operating for the isolated integrated steel-making facility
    Hsu, CT
    Cheng, HS
    CONFERENCE RECORD OF THE 2002 IEEE INDUSTRY APPLICATIONS CONFERENCE, VOLS 1-4, 2002, : 877 - 882
  • [3] Transient stability study of the large synchronous motors starting and operating for the isolated integrated steel-making facility
    Hsu, CT
    IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2003, 39 (05) : 1436 - 1441
  • [4] Protective Relay Settings of Tie Line Tripping and Load Shedding for an Integrated Steel-making Cogeneration System
    Chen, Chao-Shun
    Lisu, Cheng-Ting
    Lee, Yih-Der
    Ting, D. S.
    Shen, C. C.
    2008 IEEE INDUSTRY APPLICATIONS SOCIETY ANNUAL MEETING, VOLS 1-5, 2008, : 13 - +
  • [5] Practical Power Quality Charts for Motor Starting Assessment
    Wang, Xiaoyu
    Yong, Jing
    Xu, Wilsun
    Freitas, Walmir
    IEEE TRANSACTIONS ON POWER DELIVERY, 2011, 26 (02) : 799 - 808
  • [6] RISK ASSESSMENT OF THE INTEGRATION OF A LARGE-SCALE HYDROGEN COGENERATION FACILITY INTO A VVER POWER PLANT
    Diaz-Pescador, Eduard
    Viebach, Marco
    Gamaleja, Florian
    Hurtado, Antonio
    PROCEEDINGS OF 2024 31ST INTERNATIONAL CONFERENCE ON NUCLEAR ENGINEERING, VOL 1, ICONE31 2024, 2024,
  • [7] A Simulation Study for Power Quality Diagnosis and Optimal Solution Derivation in Steel Power Systems Affected by Large DC Mill Motor Loads
    Park, Byung-Ju
    Choi, Seok-Keun
    Transactions of the Korean Institute of Electrical Engineers, 2024, 73 (10): : 1762 - 1767