Building integrated solar air heating with waste heat utilization

被引:18
作者
Akhan, Hacer [1 ]
Eryener, Dogan [1 ]
机构
[1] Trakya Univ, Mech Engn Dept, TR-22180 Ahmet Karadeniz Yerleske, Edirne, Turkey
关键词
Solar air heating; Capillary radiant heating; Waste energy recovery; Transpired solar collector; THERMAL PERFORMANCE; SYSTEM; ENERGY; COLLECTOR; INDUSTRIAL; CONCRETE; DRYER; PUMP;
D O I
10.1016/j.enconman.2017.12.007
中图分类号
O414.1 [热力学];
学科分类号
摘要
A novel waste heat utilization system, which consists of transpired solar collector panels and capillary tube heat exchanger, is studied; its function principle is described, and its experimental performance is presented for the first time. A test unit of capillary tubes was installed at the solar wall air heater at the factory of an automotive company in Turkey in 2012. Capillary tubes utilized waste heat energy which is obtained from heat recovery unit of an air compressor. Thermal power output, ambient temperature, temperature rise, collector cavity temperatures, and water supply temperatures were monitored over the course of two winters. The results showed that capillary tubes can provide 15 degrees C temperature rise during night-time operation. The heat exchange effectiveness in air cavity is found to be maximum 0.7. The results also show that waste heat energy utilization can reach up to 85% depending on operating conditions.
引用
收藏
页码:136 / 145
页数:10
相关论文
共 29 条
[1]  
[Anonymous], 1999, 1 IEA
[2]   Transpired solar collector installations in Wales and England [J].
Brown, Catherine ;
Perisoglou, Emmanouil ;
Hall, Richard ;
Stevenson, Vicki .
PROCEEDINGS OF THE 2ND INTERNATIONAL CONFERENCE ON SOLAR HEATING AND COOLING FOR BUILDINGS AND INDUSTRY (SHC 2013), 2014, 48 :18-27
[3]  
Carpenter S., 2002, Proceedings eSim, P11
[4]  
D'Agostino O, 2017, ENERGY BUILD, V153, P2
[5]  
Eryener D, 2012, 9 INT C HEAT TRANSF
[6]   The performance of first transpired solar collector installation in Turkey [J].
Eryener, Dogan ;
Akhan, Hacer .
PROCEEDINGS OF THE 4TH INTERNATIONAL CONFERENCE ON SOLAR HEATING AND COOLING FOR BUILDINGS AND INDUSTRY (SHC 2015), 2016, 91 :442-449
[7]   Improvement of waste heat recuperation on an industrial textile dryer: Redesign of heat exchangers network and components [J].
Fiaschi, Daniele ;
Manfrida, Giampaolo ;
Russo, Luigi ;
Talluri, Lorenzo .
ENERGY CONVERSION AND MANAGEMENT, 2017, 150 :924-940
[8]  
Gourlis G, 2014, APPL ENERG, V184, P1389
[9]   Flow distribution in unglazed transpired plate solar air heaters of large area [J].
Gunnewiek, LH ;
Brundrett, E ;
Hollands, KGT .
SOLAR ENERGY, 1996, 58 (4-6) :227-237
[10]   UNGLAZED SOLAR WALL AIR HEATERS [J].
HOLLICK, JC .