Electrical Power Quality of Iron and Steel Industry in Turkey

被引:0
作者
Salor, Oe. [1 ]
Gueltekin, B. [1 ]
Buhan, S. [1 ]
Boyrazoglu, B. [1 ]
Inan, T. [1 ]
Atalik, T. [1 ]
Acik, A. [1 ]
Terciyanli, A. [1 ]
Uensar, Oe [2 ]
Altintas, E. [2 ]
Akkaya, Y. [2 ]
Oezdemirci, E. [2 ]
Cadirci, I. [1 ,4 ]
Ermis, M. [3 ]
机构
[1] TUBITAK UZAY, Power Elect Grp, Ankara, Turkey
[2] Turkish Elect Transmiss Co, Ankara, Turkey
[3] Middle East Tech Univ, Ankara, Turkey
[4] Hacettepe Univ, Ankara, Turkey
来源
CONFERENCE RECORD OF THE 2007 IEEE INDUSTRY APPLICATIONS CONFERENCE FORTY-SECOND IAS ANNUAL MEETING, VOLS. 1-5 | 2007年
关键词
power quality; iron and steel industry; arc furnace; ladle furnace; interharmonics; flicker; single-line harmonic; group harmonic; subgroup harmonic; interharmonic-flicker relation;
D O I
暂无
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
Iron and Steel Industry has been growing increasingly in Turkey in the last decade. Today its electricity demand is nearly one tenth of the installed generation capability of 40 GW in the country. In this paper, power quality investigations based on the arc furnace installations of the iron and steel plants using field measurements according to the international standard IEC 61000-4-30 are documented. Inter-harmonies and voltage flicker problems occurring both at the common coupling points of those plants and at the are furnace and SVC systems of the plants themselves are determined with the use of GPS receiver synchronization modules attached to the mobile power quality measurement systems. It has been observed that flicker and interharmonic problems are dominant at the point of common couplings where arc furnace installations are supplied. Based on the field measurements obtained with collaborative work of five arc furnace plants, it is possible to say that contemporary SVC systems cause interharmonic amplification problems around the second harmonic and novel methods are required to solve this problem.
引用
收藏
页码:404 / +
页数:2
相关论文
共 20 条
[1]  
[Anonymous], 61000415 IEC
[2]  
[Anonymous], 6100047 IEC
[3]  
[Anonymous], 5191992 IEEE
[4]   ARC FURNACE FLICKER MEASUREMENTS AND CONTROL [J].
BHARGAVA, B ;
WILHELM, MR .
IEEE TRANSACTIONS ON POWER DELIVERY, 1993, 8 (01) :400-410
[5]  
BOULET B, 1997, IEEE IND APPL SOC AN
[6]  
DEMIRCI T, IEEE INSTR MEAS TECH
[7]  
HERNANDEZ A, 2005, IEEE T POWER DELIVER, V29
[8]  
IEC, 6100430 IEC
[9]  
*IEEE, STD1159 IEEE
[10]  
ISSOURIBEHERE PE, 2005, POWER QUALITY OPERAT