The cooling heat transfer characteristics of the supercritical CO2 in micro-fin tube

被引:30
作者
Lee, Ho-Saeng [1 ]
Kim, Hyeon-Ju [1 ]
Yoon, Jung-In [2 ]
Choi, Kwang-Hwan [2 ]
Son, Chang-Hyo [2 ]
机构
[1] Korea Inst Ocean Sci & Technol, Deep Ocean Water Applicat Res Ctr, Goseong Gun 219822, Gangwon Do, South Korea
[2] Pukyong Natl Univ, Dept Refrigerat & Air Conditioning Engn, Pusan 608739, South Korea
关键词
CARBON-DIOXIDE;
D O I
10.1007/s00231-012-1070-2
中图分类号
O414.1 [热力学];
学科分类号
摘要
This study intended to verify the cooling heat transfer characteristics of supercritical gas for refrigerating and air-conditioning devices that use CO2, a natural refrigerant, as the operating fluid. Experiments were performed with a gas cooler, which was the test part. The gas cooler was a heat exchanger made of a micro-fin tube with an inner diameter of 4.6 mm and an outer diameter of 5.0 mm. The experiment results are summarized as follows. The heat transfer coefficient, according to the mass flux, peaked at the low cooling pressure of 8.0 MPa in the gas cooler, and reached its minimum at the high pressure of 10.0 MPa. Furthermore, when the mass flux of the refrigerant increased, the coefficient increased faster with the lower cooling pressure in the gas cooler. The heat transfer coefficient, according to the shape of the heat transfer tube, showed that the maximum values of the CO2 cooling heat transfer coefficients of the smooth tube and the micro-fin tube were found at 44.7 A degrees C, which were the pseudo-critical temperatures for the entrance pressures. It was found that the cooling heat transfer coefficient of the micro-fin tube increased by 12-39 % more than that of the smooth tube. The experiment results for the CO2 heat transfer coefficients of the smooth tube and the micro-fin tube were compared with the results estimated from previous correlations. It was found that the experiment values generally significantly differed from and the experiment values greater than the estimated values. The differences were especially greater in the vicinity of the critical temperature points. Based on these results, a new correlation was suggested that includes the density ratio and the specific heat ratio.
引用
收藏
页码:173 / 184
页数:12
相关论文
共 26 条
[1]  
[Anonymous], 2002, P ASIAN C REFRIGERAT
[2]  
[Anonymous], 2002, P ASIAN C REFRIGERAT
[3]  
BASKOV VL, 1977, TEPLOFIZ VYS TEMP, V15, P96
[4]  
BODINUS WS, 1999, 1 CENTURY AIR CONDIT, P29
[5]   Heat transfer and pressure drop during condensation of refrigerants inside horizontal enhanced tubes [J].
Cavallini, A ;
Del Col, D ;
Doretti, L ;
Longo, GA ;
Rossetto, L .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2000, 23 (01) :4-25
[6]  
Dang C, 2003, COOLING HEAT TRANSFE
[7]  
Dang C, 2002, P AS C REFR AIR COND, P60
[8]   Effect of PAG-type lubricating oil on heat transfer characteristics of supercritical carbon dioxide cooled inside a small internally grooved tube [J].
Dang, Chaobin ;
Iino, Koji ;
Hihara, Eiji .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2010, 33 (03) :558-565
[9]  
Dittus F.W., 1985, Int. Commun. Heat Mass, V12, P3, DOI [10.1016/0735-1933(85)90003-X, DOI 10.1016/0735-1933(85)90003-X]
[10]  
Donaldson B., 1994, Heat Cold: Mastering the Great Indoors