Islanding detection method based on a Thevenin-like model

被引:2
作者
Di Fazio, Anna Rita [1 ]
Fusco, Giuseppe [1 ]
Russo, Mario [1 ]
机构
[1] Univ Cassino & Lazio Merid, Dipartimento Ingn Elettr & Informaz, I-03043 Cassino, FR, Italy
关键词
SYSTEM; GENERATION; PROTECTION; RELAYS; SCHEME; POWER;
D O I
10.1049/iet-gtd.2014.0721
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Reliable detection of islanded operation is essential in distribution systems with large penetration of the distributed generation. Commonly-used protections present performance limitations in terms of sensitivity and stability. To overcome such limitations, this study proposes to enrich classical protections by adding a passive islanding detector based on a new method. It adopts a linear representation of the low voltage distribution system, referred to as Thevenin-like model. On the basis of the voltage and current measures at the detector installation point, two model parameters are estimated and are used to distinguish islanded from grid-connected operation. The proposed detector presents high sensitivity and reliability, does not require expert tuning, can be installed in different points of the distribution system and is economically viable. Numerical analysis and simulations, evidence the effectiveness of the proposed method.
引用
收藏
页码:1747 / 1754
页数:8
相关论文
共 25 条
[1]   An Autoground System for Anti-Islanding Protection of Distributed Generation [J].
Abbey, Chad ;
Brissette, Yves ;
Venne, Philippe .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2014, 29 (02) :873-880
[2]   Performance of ROCOF relays for embedded generation applications [J].
Affonso, CM ;
Freitas, W ;
Xu, W ;
da Silva, LCP .
IEE PROCEEDINGS-GENERATION TRANSMISSION AND DISTRIBUTION, 2005, 152 (01) :109-114
[3]  
[Anonymous], 2004, 61727 IEC
[4]  
[Anonymous], 2008, 1547 IEEE
[5]   Anti-Islanding Scheme for Synchronous DG Units Based on Tufts-Kumaresan Signal Estimation Method [J].
Bakhshi, Mohsen ;
Noroozian, Reza ;
Gharehpetian, G. B. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2013, 28 (04) :2185-2193
[6]  
Di Fazio A. R., 2014, 3 IET REN POW GEN C, P1
[7]   A smart device for islanding detection in distribution system operation [J].
Di Fazio, Anna Rita ;
Fusco, Giuseppe ;
Russo, Mario ;
Valeri, Sara ;
Noce, Christian ;
Amura, Giuseppe .
ELECTRIC POWER SYSTEMS RESEARCH, 2015, 120 :87-95
[8]   UK distribution system protection issues [J].
Dysko, A. ;
Burt, G. M. ;
Galloway, S. ;
Booth, C. ;
McDonald, J. R. .
IET GENERATION TRANSMISSION & DISTRIBUTION, 2007, 1 (04) :679-687
[9]   Reducing unnecessary disconnection of renewable generation from the power system [J].
Dysko, A. ;
Booth, C. ;
Anaya-Lara, O. ;
Burt, G. M. .
IET RENEWABLE POWER GENERATION, 2007, 1 (01) :41-48
[10]  
Dysko A., 2010, DEV POW SYST PROT DP, P1