Effect of temperature on flow electrification under dc electrical field

被引:5
作者
Gao, Yuan [1 ]
Li, Feng [1 ]
Lu, Wu [1 ]
Zhao, Wenbin [1 ]
机构
[1] Shanghai Univ Elect Power, Coll Elect Engn, Shanghai, Peoples R China
来源
JOURNAL OF ENGINEERING-JOE | 2019年 / 16期
关键词
transformer oil; power transformer insulation; power convertors; mathematical analysis; velocity; 1; 2; m; s; 0; mathematic model; inverted U-shaped development; streaming current measurement; converter transformer turn-to-turn insulation structure simulation; flow electrification temperature effect; high flow velocity; low flow velocity; oil-pressboard insulation system; STREAMING ELECTRIFICATION; AC;
D O I
10.1049/joe.2018.8367
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
An oil-pressboard insulation system has been built to simulate converter transformer turn-to-turn insulation structure. Streaming current in the oil was measured while applying high dc voltage on the insulation at different temperatures. Flow electrification was also researched at low flow velocity of 0.2m/s and at high flow velocity of 1.2m/s. The streaming current increases exponentially with temperature when the high dc voltage is not applied on the insulation. However, at the same temperature, the streaming current is much smaller than that with the dc voltage been applied. The streaming current is in an inverted U-shaped development with the increase of temperature, when the insulation withstands the dc voltage. The peak value of the streaming current was observed at a lower temperature when the dc voltage is higher. A mathematic model has been developed to describe the electrification characteristics of insulation under the dc voltage.
引用
收藏
页码:2893 / 2896
页数:4
相关论文
共 9 条
[1]   Flow Electrification Characteristics of Oil-pressboard Insulation under AC Superimposed on DC Electric Field [J].
Chen, Qingguo ;
Lin, Lin ;
Gao, Yuan ;
Li, Jiahui .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2015, 22 (05) :2915-2922
[2]  
Dai J, 2017, 2017 INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATING MATERIALS (ISEIM), VOLS 1 & 2, P687, DOI 10.23919/ISEIM.2017.8166583
[3]  
Dai J, 2016, C ELECT INSUL DIEL P, P66, DOI 10.1109/CEIDP.2016.7785441
[4]  
Lin J. Z., 2012, FLUID MECH, P224
[5]   Flow electrification of transformer oil effects of mixed fields [J].
Metwally, IA .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 1998, 5 (04) :518-526
[6]   INFLUENCE OF AC AND DC FIELDS ON STREAMING ELECTRIFICATION OF TRANSFORMER OIL [J].
MIYAO, H ;
HIGAKI, M ;
KAMATA, Y .
IEEE TRANSACTIONS ON ELECTRICAL INSULATION, 1988, 23 (01) :129-135
[7]   INVESTIGATION OF STATIC ELECTRIFICATION PHENOMENON DUE TO TRANSFORMER OIL FLOW IN ELECTRIC-POWER APPARATUS [J].
RADWAN, RM ;
ELDEWIENY, RM ;
METWALLY, IA .
IEEE TRANSACTIONS ON ELECTRICAL INSULATION, 1992, 27 (02) :278-286
[8]   dc field effects on streaming electrification in insulating oils [J].
Wu, H ;
Jayaram, S .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 1996, 3 (04) :499-506
[9]   Study of the influence of injected charge on streaming electrification [J].