Fire accident investigation of an explosion caused by static electricity in a propylene plant

被引:19
作者
Chou, Hung-Cheng [1 ]
Yeh, Chi-Tang [1 ]
Shu, Chi-Min [2 ]
机构
[1] Natl Yunlin Univ Sci & Technol YunTech, Grad Sch Engn Sci & Technol, Doctoral Program, Touliu 64002, Yunlin, Taiwan
[2] Natl Yunlin Univ Sci & Technol, Dept Safety Hlth & Environm Engn, Touliu 64002, Yunlin, Taiwan
关键词
Fire and explosion; Liquid acetone leakage; Acetone storage tank; Burning (bursting) loss; Static electricity; Flammable liquids;
D O I
10.1016/j.psep.2015.02.007
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
This study investigated a 2010 fire and explosion that occurred at a polypropylene (PP) and copper-clad laminate high-tech plant in Taiwan. Liquid acetone leakage caused the fire and explosion. One person was killed and five were injured; property damage was estimated at US$20 million. In contrast to conventional plants, high-tech plants have sophisticated instrumentation, highly complex pipelines, and confined spaces. In addition, the floor area in a high-tech plant is large and frequently contains a channel through the ground floor to the second or third floor. This channel design enables the fire compartment to be destroyed. Therefore, the system cannot confine the fire to a specific area, thus hindering fire-relief operations. In this study, the original fire outbreak occurred in the PP processing area on the ground floor. The acetone storage tank was located on the third floor. The investigation conducted at the fire site of the situations of the burning (bursting) loss determined that the acetone liquid leaked and dripped from floor cracks and tunnel oven to the PP processing area. Because the PP manufacturing process rapidly generates static electricity, the flammable liquids made contact with the source of ignition, which caused the explosion and fire. Various procedures, such as those involving the operating environment of production, packaging, and processing in a high-tech plant, are likely to produce static electricity in a workplace. Improved electrostatic management can prevent the loss of property and lives, liquid acetone leakage, and loss of equipment caused by static electricity fire. (C) 2015 The Institution of Chemical Engineers. Published by Elsevier B.V. All rights reserved.
引用
收藏
页码:116 / 121
页数:6
相关论文
共 9 条
  • [1] Chan J.H., 2010, The Development of Industrial Fire Investigation Technology and Cases Study
  • [2] Thermal hazard accident investigation of hydrogen peroxide mixing with propanone employing calorimetric approaches
    Chi, Jen-Hao
    Wu, Sheng-Hung
    Charpentier, Jean-Claude
    Yet-Pole, I
    Shu, Chi-Min
    [J]. JOURNAL OF LOSS PREVENTION IN THE PROCESS INDUSTRIES, 2012, 25 (01) : 142 - 147
  • [3] Quantitative risk analysis of fire and explosion on the top-side LNG-liquefaction process of LNG-FPSO
    Dan, Seungkyu
    Lee, Chang Jun
    Park, Jeongpil
    Shin, Dongil
    Yoon, En Sup
    [J]. PROCESS SAFETY AND ENVIRONMENTAL PROTECTION, 2014, 92 (05) : 430 - 441
  • [4] Hsieh W.K., 2014, Performance Evaluation of Fire Protection Systems in High-Tech Facilities
  • [5] Li M.C., 2014, THESIS WU FENG U SCI
  • [6] Lin H.Y., 2014, THESIS NATL TAIWAN U
  • [7] National Fire Agency (NFA) Ministry of the Interior Executive Yuan Taiwan, 2009, ID STAND OP PROC FIR
  • [8] Fire and explosion assessment on oil and gas floating production storage offloading (FPSO): An effective screening and comparison tool
    Suardin, Jaffee A.
    McPhate, A. Jeff, Jr.
    Sipkema, Anthony
    Childs, Matt
    Mannan, M. Sam
    [J]. PROCESS SAFETY AND ENVIRONMENTAL PROTECTION, 2009, 87 (03) : 147 - 160
  • [9] Ye C.M., 2014, THESIS CENTRAL TAIWA