Novel and Necessary Assessment Procedure Ensuring UHF Partial Discharge On-line Supervision System Effective for GIS/GIL

被引:0
作者
Liu, Yang [1 ]
Qi, Weidong [1 ]
Wu, Jingfeng [1 ]
Pu, Lu [1 ]
Ding, Bin [1 ]
Yang, Chuankai [1 ]
Zhang, Ziqi [2 ]
Chen, Siyu [2 ]
机构
[1] State Grid Shaanxi Elect Power Res Inst, Power Equipment Assessment Ctr, Xian, Shaanxi, Peoples R China
[2] State Grid Xian Elect Power Supply Co, Dept Operat & Maintenance, Xian, Shaanxi, Peoples R China
来源
2017 4TH INTERNATIONAL CONFERENCE ON ELECTRIC POWER EQUIPMENT-SWITCHING TECHNOLOGY (ICEPE-ST) | 2017年
关键词
assessment procedure; effective height; GIS/GIL; on-line supervision; UHF PD;
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
To better assess the effectivity of UHF-PD sensor/system, two types of assessment procedures were established-the simple procedure and the complicated procedure. Both procedure required GTEM-Cell system and Simulation GIS/GIL. The element structure, the diagram and the signal transmission path of GTEM-Cell system and the Simulation GIS/GIL were demonstrated. The result data indicated that the discernment of the procedure was better with more tests. The procedure covered 90% of known defects or failure cases of UHF-PD sensor/system.
引用
收藏
页码:803 / 807
页数:5
相关论文
共 15 条
[1]  
[Anonymous], 2017, 116452016 STAT GRID
[2]  
[Anonymous], 2015, 112822014 STAT GRID
[3]  
[Anonymous], 2014, 1105922013 STAT GRID
[4]  
Aschenbrenner D., P 2005 IEEE EL INS M, P687
[5]  
Hoshino T., P 2012 IEEE PES TRAN, P798
[6]  
Judd M. D., P 2002 IEEE EL INS S, P407
[7]  
Li X. W., P 2012 IEEE HIGH VOL, P625
[8]  
Li Xing-wang, 2012, High Voltage Apparatus, V48, P70
[9]  
Liu Y., P 2017 IEEE EL MAT P, P618
[10]  
Liu Y, 2016, INT CONF CONDIT MON, P307, DOI 10.1109/CMD.2016.7757812