Performance analysis of finned-tube CO2 gas cooler with advanced 1D-3D CFD modelling development and simulation

被引:8
作者
Zhang, X. Y. [1 ]
Ge, Y. T. [1 ]
Sun, J. N. [2 ]
机构
[1] Univ South Wales, Fac Comp Engn & Sci, Sustainable Environm Res Ctr, Pontypridd CF37 1DL, M Glam, Wales
[2] Brunel Univ London, RCUK Natl Ctr Sustainable Energy Use Food Chains, Inst Energy Future, Uxbridge UB8 3PH, Middx, England
基金
英国工程与自然科学研究理事会;
关键词
CO2 finned-tube gas cooler; Thermal conduction through fins; Refrigeration system efficiency; Computational Fluid Dynamics (CFD) modelling; Air flow maldistribution; PRESSURE-DROP CHARACTERISTICS; HEAT-TRANSFER; HYBRID METHOD; PLATE-FIN; EXCHANGERS; FLOW; COOLER/CONDENSER; CYCLES; SYSTEM;
D O I
10.1016/j.applthermaleng.2020.115421
中图分类号
O414.1 [热力学];
学科分类号
摘要
Due to natural refrigerant applied, CO2 transcritical refrigeration and heat pump systems have been widely applied and attracted more attentions. As a main component, CO2 gas cooler plays an important role in the system performance and thus requires further development for design and control optimizations with advanced technology. Correspondingly, a new coupled 1D and 3D Computational Fluid Dynamics (CFD) model on a finned-tube CO2 gas cooler has been proposed and developed. The CFD model has been validated by comparing with literatures for parameters including airside heat transfer coefficient, refrigerant side temperature profile as well as heating capacity. The model has been applied to predict the heat exchanger performance at different operating conditions of both air and refrigerant sides and maldistributions of air flow inlet. It is found from the simulation results that the refrigerant temperature decreases abruptly in the first coil row and the refrigerant temperature profile along the heat exchanger tubes is affected by thermal conduction between two adjacent tube rows through fins. In addition, the higher air flow inlet velocity can reduce greatly the coil approach temperature and thus improve the system efficiency. Similar effect can also be found from refrigerant pressure. Furthermore, the non-uniform air flow patterns can affect considerably the coil performance in terms of the refrigerant temperature profile, coil approach temperature, coil heating capacity and system energy efficiency. The developed CFD model can be an efficient tool for the performance evaluation and optimisation of the CO(2 )gas cooler and its associated system.
引用
收藏
页数:15
相关论文
共 24 条
[1]  
[Anonymous], DOECE2381081
[2]   Three-dimensional performance analysis of plain fin tube heat exchangers in transitional regime [J].
Bhuiyan, Arafat A. ;
Amin, M. Ruhul ;
Islam, A. K. M. Sadrul .
APPLIED THERMAL ENGINEERING, 2013, 50 (01) :445-454
[3]   In-tube cooling heat transfer of supercritical carbon dioxide. Part 1. Experimental measurement [J].
Dang, C ;
Hihara, E .
INTERNATIONAL JOURNAL OF REFRIGERATION, 2004, 27 (07) :736-747
[4]   Effect of geometrical parameters on heat transfer and pressure drop characteristics of plate fin and tube heat exchangers [J].
Erek, A ;
Özerdem, B ;
Bilir, L ;
Ilken, Z .
APPLIED THERMAL ENGINEERING, 2005, 25 (14-15) :2421-2431
[5]   Numerical investigations on two-phase flow modes in evaporative condensers [J].
Fiorentino, Maria ;
Starace, Giuseppe .
APPLIED THERMAL ENGINEERING, 2016, 94 :777-785
[6]   Design optimisation of CO2 gas cooler/condenser in a refrigeration system [J].
Ge, Y. T. ;
Tassou, S. A. ;
Santosa, I. Dewa ;
Tsamos, K. .
APPLIED ENERGY, 2015, 160 :973-981
[7]   Simulation and performance evaluation of finned-tube CO2 gas coolers for refrigeration systems [J].
Ge, Y. T. ;
Cropper, R. T. .
APPLIED THERMAL ENGINEERING, 2009, 29 (5-6) :957-965
[8]   Control optimisatlion of CO2 cycles for medium temperature retail food refrigeration systems [J].
Ge, Y. T. ;
Tassou, S. A. .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2009, 32 (06) :1376-1388
[9]  
GNIELINSKI V, 1976, INT CHEM ENG, V16, P359
[10]  