Faulty line detection method based on improved Hilbert-Huang transform for resonant grounding systems

被引:8
作者
Song, Jinzhao [1 ]
Li, Yongli [1 ]
Zhang, Yunke [1 ]
机构
[1] Tianjin Univ, Sch Elect & Informat Engn, Tianjin, Peoples R China
关键词
faulty line detection; high frequency component; Hilbert margin spectrum; improved Hilbert‐ Huang transform; resonant grounding system;
D O I
10.1002/2050-7038.12760
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Detecting a line experiencing single-phase-to-ground fault in a resonant grounding system is difficult due to weak fault current and low differentiation between the faulty line and healthy line. To overcome this difficulty, a novel faulty line detection method based on improved Hilbert-Huang transform is proposed in this article. The method consists of two parts: Hilbert marginal spectrum method (HMSM) and high frequency component method. HMSM is used for faulty line preliminary detection. Using this method, the zero-sequence current of each feeder is decomposed into several intrinsic mode functions, which represent the components of signals at different time scales by ensemble empirical model decomposition. Then, the Hilbert marginal spectrum energy of the characteristic frequency band of each feeder is calculated, and three feeders with the greatest energy are selected as the preliminary result. High frequency component method is then used to further distinguish feeder fault and busbar fault and provide a final detection result. It first reconstructs high frequency signals of the zero-sequence current, and then detects the faulty line by comparing the polarities of the signals. Simulation results show that the new method can precisely detect a faulty line in various fault conditions.
引用
收藏
页数:15
相关论文
共 41 条
  • [31] Tian You Li, 2017, CIRED - Open Access Proceedings Journal, V2017, P1176, DOI 10.1049/oap-cired.2017.0565
  • [32] Identification of the Faulted Distribution Line Using Thyristor-Controlled Grounding
    Wang, Wencong
    Zhu, Ke
    Zhang, Peng
    Xu, Wilsun
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2009, 24 (01) : 52 - 60
  • [33] How to Choose "Last Mile'' Delivery Modes for E-Fulfillment
    Wang, Xuping
    Zhan, Linmin
    Ruan, Junhu
    Zhang, Jun
    [J]. MATHEMATICAL PROBLEMS IN ENGINEERING, 2014, 2014
  • [34] Faulty Feeder Detection of Single Phase-Earth Fault Using Grey Relation Degree in Resonant Grounding System
    Wang, Yuanyuan
    Huang, Yuhao
    Zeng, Xiangjun
    Wei, Gen
    Zhou, Jiaming
    Fang, Tao
    Chen, Haowei
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2017, 32 (01) : 55 - 61
  • [35] Fault Detection Based on the Generalized S-Transform With a Variable Factor for Resonant Grounding Distribution Networks
    Wei, Zhinong
    Mao, Yuexuan
    Yin, Zhihua
    Sun, Guoqiang
    Zang, Haixiang
    [J]. IEEE ACCESS, 2020, 8 (08): : 91351 - 91367
  • [36] Improved Wavelet Denoising by Non-Convex Sparse Regularization Under Double Wavelet Domains
    Wu, Yongjun
    Gao, Guangjun
    Cui, Can
    [J]. IEEE ACCESS, 2019, 7 : 30659 - 30671
  • [37] Xu, 2010, POWER SYST PROTECT C, V38, P86
  • [38] Resonance Analysis and Faulty Feeder Identification of High-Impedance Faults in a Resonant Grounding System
    Xue, Yongduan
    Chen, Xiaoru
    Song, Huamao
    Xu, Bingyin
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2017, 32 (03) : 1545 - 1555
  • [39] [薛永端 Xue Yongduan], 2015, [中国电机工程学报, Proceedings of the Chinese Society of Electrical Engineering], V35, P5703
  • [40] A New Shift-Invariance of Discrete-Time Systems and Its Application to Discrete Wavelet Transform Analysis
    Yu, Runyi
    [J]. IEEE TRANSACTIONS ON SIGNAL PROCESSING, 2009, 57 (07) : 2527 - 2537