Statistical approach for transient stability constrained optimal power flow

被引:14
作者
Zerigui, Amel [1 ]
Dessaint, Louis-A. [1 ]
Hannat, Ridha [2 ]
Ah King, Robert T. F. [1 ,3 ]
Kamwa, Innocent [4 ]
机构
[1] Ecole Technol Super, Dept Elect Engn, Montreal, PQ H3C 1K3, Canada
[2] Ecole Technol Super, Dept Mech Engn, Montreal, PQ H3C 1K3, Canada
[3] Univ Mauritius, Dept Elect & Elect Engn, Reduit 80837, Mauritius
[4] Inst Rech Hydro Quebec IREQ, Reseaux Elect & Math, Varennes, PQ J3X 1S1, Canada
关键词
load flow; power system transient stability; Pareto analysis; design of experiments; interpolation; statistical approach; transient stability constrained optimal power flow; TSC-OPF; power systems; space interpolation method; design of experiment; optimisation process; stability constraint; optimisation problem; England 10-machine 39-bus system; 50-machine 145-bus power system; SYSTEMS; NETWORK;
D O I
10.1049/iet-gtd.2014.0689
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The transient stability constrained optimal power flow (TSC-OPF) is a big challenge in the field of power systems because of its high complexity and extensive computation effort involved in its solution. This study presents a new approach to compute the transient stability constraint formulated by the critical clearing time (CCT) in TSC-OPF. CCT has been determined by dual-kriging, a space interpolation method which has primarily been used in natural resources evaluation. Given the huge dimensionality of the problem, Pareto analysis is firstly used to reduce the number of input variables in an initial database to those which are significant to compute CCT. With the reduced variables, a new database has been constructed using a design of experiment to obtain a reduced number of observed points. As a result of this approach, the sets of dynamic and transient stability constraints to be considered in the optimisation process are reduced to one single stability constraint with only a few variables. Ultimately, the size of the resulting optimisation problem is almost similar to that of a conventional optimal power flow. The effectiveness of the proposed method is tested on the New England 10-machine 39-bus system and the larger 50-machine 145-bus power system.
引用
收藏
页码:1856 / 1864
页数:9
相关论文
共 32 条
  • [1] [Anonymous], THESIS U MANITOBA
  • [2] Application of differential evolution algorithm for transient stability constrained optimal power flow
    Cai, H. R.
    Chung, C. Y.
    Wong, K. P.
    [J]. IEEE TRANSACTIONS ON POWER SYSTEMS, 2008, 23 (02) : 719 - 728
  • [3] Optimal operation solutions of power systems with transient stability constraints
    Chen, LN
    Tada, Y
    Okamoto, H
    Tanabe, R
    Ono, A
    [J]. IEEE TRANSACTIONS ON CIRCUITS AND SYSTEMS I-FUNDAMENTAL THEORY AND APPLICATIONS, 2001, 48 (03): : 327 - 339
  • [4] Optimal generation rescheduling with sensitivity-based transient stability constraints
    Fang, D. Z.
    Sun, W.
    Xue, Z. Y.
    [J]. IET GENERATION TRANSMISSION & DISTRIBUTION, 2010, 4 (09) : 1044 - 1051
  • [5] Stability-constrained optimal power flow
    Gan, DQ
    Thomas, RJ
    Zimmerman, RD
    [J]. IEEE TRANSACTIONS ON POWER SYSTEMS, 2000, 15 (02) : 535 - 540
  • [6] Decision Tree-Based Preventive and Corrective Control Applications for Dynamic Security Enhancement in Power Systems
    Genc, Istemihan
    Diao, Ruisheng
    Vittal, Vijay
    Kolluri, Sharma
    Mandal, Sujit
    [J]. IEEE TRANSACTIONS ON POWER SYSTEMS, 2010, 25 (03) : 1611 - 1619
  • [7] Juran J. M., 1998, JURANS QUALITY HDB
  • [8] Transient stability assessment of power systems described with detailed models using neural networks
    Karami, A.
    Esmaili, S. Z.
    [J]. INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2013, 45 (01) : 279 - 292
  • [9] Application of a stability-constrained optimal power flow to tuning of oscillation controls in competitive electricity markets
    Kodsi, Sameh K. A.
    Canizares, Claudio A.
    [J]. IEEE TRANSACTIONS ON POWER SYSTEMS, 2007, 22 (04) : 1944 - 1954
  • [10] KRIGE DG, 1994, J S AFR I MIN METALL, V94, P95